Plan Review Notes For Permit 10070389
Permit Number 10070389
Review Stop E
Sequence Number 1
Notes
Date Text
2010-07-21 12:43:43 
  
 REVISION DENIED
  
 1} THE DESIGNER OF RECORD IS THE ONLY PERSON AUTHORIZED
 TO REVISE HIS/HER PLAN. TAKE ALL PROPOSED CHANGES TO
 THE DESIGNER TO BE REDRAWN.
  
 2} 210.62 SHOW WINDOWS.
 AT LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED
 WITHIN 450 MM (18 IN.) OF THE TOP OF A SHOW WINDOW FOR
 EACH 3.7 LINEAR M (12 LINEAR FT) OR MAJOR FRACTION
 THEREOF OF SHOW WINDOW AREA MEASURED HORIZONTALLY AT
 ITS MAXIMUM WIDTH.***INDICATE LOCATION ON PLANS AND ADD
 TO PANEL SCHEDULE.
  
 3} 220.43 SHOW-WINDOW AND TRACK LIGHTING.
 (A) SHOW WINDOWS. FOR SHOW-WINDOW LIGHTING, A LOAD OF
 NOT LESS THAN 660 VOLT-AMPERES/LINEAR METER OR 200
 VOLT-AMPERES/LINEAR FOOT SHALL BE INCLUDED FOR A SHOW
 WINDOW, MEASURED HORIZONTALLY ALONG ITS BASE.
  
 NOTE: THE PANEL CAND CIRCUIT DESIGNATION NUMBERS ARE
 "M" ON THE PERMIT SET OF PLANS AND "A" ON THE REVISION,
 CORRELATE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  