| Plan Review Notes For Permit 10070338 |
| Permit Number |
10070338 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-04 10:49:58 | 1801 SOUTH FLAGLER DRIVE, UNIT 803 | | | PERMIT NUMBER 10070338 | | | REMODELING OF EXISTING CONDOMINIUM UNIT | | | | | | | | | 1. PLANS DO NOT INDICATE IF AN EXISTING FIRE SPRINKLER | | | SYSTEM IS PRESENT. PLEASE ADVISE IF FIRE SPRINKLER | | | SYSTEM IS PRESENT. | | | | | | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 3. DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. | | | | | | 4. CONSTRUCTION DEBRIS AND ACTIVITIES SHALL NOT | | | INTERFERE WITH ANY REQUIRED EXITS FROM THE BUILDING. | | | | | | 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | | WALLS AND CEILINGS WITHIN THE UNIT. | | | | | | 6. PLEASE ENSURE THAT THE EXISTING SMOKE ALARMS ARE IN | | | GOOD WORKING ORDER. | | | | | | 7. PLANS DO NOT INDICATE THE LOCATIONS OF ANY EXISTING | | | FIRE ALARM EQUIPMENT CONTAINED WITHIN OR IMMEDIATELY | | | OUTSIDE OF UNIT. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | |
|