Plan Review Notes
Plan Review Notes For Permit 10070313
Permit Number 10070313
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-07-23 13:18:49*****DENIED*****
  
 1) LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE FRONT DOORS SHALL AUTOMATICALLY
 UNLOCK THE DOORS IN THE DIRECTION OF EGRESS.
 2) THE MANUAL DOOR RELEASE DEVICE SHALL BE UNOBSTRUCTED
 AND READ, ???PUSH TO EXIT???. WHEN PUSHED, THE MANUAL
 RELEASE DEVICE SHALL RESULT IN DIRECT INTERRUPTION OF
 POWER TO THE LOCK-INDEPENDENT OF THE ACCESS CONTROL
 SYSTEM ELECTRONICS-AND THE DOORS SHALL REMAIN UNLOCKED
 FOR NOT LESS THAN 30 SECONDS.
 3) ACTIVATION OF THE BUILDING FIRE DETECTION SYSTEM OR
 SIGNALING SYSTEM SHALL AUTOMATICALLY UNLOCK THE DOORS
 IN THE DIRECTION OF EGRESS.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
  