| Plan Review Notes For Permit 10070277 |
| Permit Number |
10070277 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-23 13:13:31 | *****DENIED***** | | | | | | 1) PROVIDE CORRECT ADDRESS; 400 NORTH FLAGLER DRIVE NOT | | | 400 SOUTH FLAGLER DRIVE | | | 2) HVAC DUCT DETECTORS SHALL INITIATE A GENERAL FIRE | | | ALARM CONDITION. | | | 3) PROVIDE SMOKE ALARMS OUTSIDE EVERY SLEEPING AREA. | | | 4) PROVIDE ANNUNCIATOR PANEL | | | 5) DEVICE ADDRESSES NOT GIVEN | | | 6) PLEASE PROVIDE WHAT VOICE EVACUATION MESSAGE WILL | | | SAY | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 | | | |
|