| 2010-07-15 12:01:49 | 2007 FBC W/2009 REVISIONS | | | 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) THE NAME, LICENSE NUMBER AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE ELECTRICAL DESIGN IS REQUIRED ON | | | THE PLANS. SEE BUILDING REVIEW COMMENTS. | | | | | | 2) SHOW COMPLIANCE WITH 2008 NEC 210.52 FOR RECEPTACLE | | | SPACING, 210.12 FOR ARC-FAULT AND FOR TAMPER-PROOF | | | RECEPTACLES IN THE NEW WALLS. | | | | | | 3) SMOKE ALARMS SHALL BE INSTALLED IN ACCORDANCE WITH | | | FBC R313.2.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|