Plan Review Notes
Plan Review Notes For Permit 10070257
Permit Number 10070257
Review Stop E
Sequence Number 1
Notes
Date Text
2010-07-15 12:01:492007 FBC W/2009 REVISIONS
 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) THE NAME, LICENSE NUMBER AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE ELECTRICAL DESIGN IS REQUIRED ON
 THE PLANS. SEE BUILDING REVIEW COMMENTS.
  
 2) SHOW COMPLIANCE WITH 2008 NEC 210.52 FOR RECEPTACLE
 SPACING, 210.12 FOR ARC-FAULT AND FOR TAMPER-PROOF
 RECEPTACLES IN THE NEW WALLS.
  
 3) SMOKE ALARMS SHALL BE INSTALLED IN ACCORDANCE WITH
 FBC R313.2.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW