| Plan Review Notes For Permit 10070239 |
| Permit Number |
10070239 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-23 13:08:51 | *****DENIED***** | | | | | | 1) PROVIDE ADDRESS IN TITLEBLOCK | | | 2) PROVIDE SUPPRESSION COVERAGE IN EXHAUST PLENUM AND | | | EXHAUST DUCTWORK PER NFPA 33 (2003 ED.), SECTION 9.5. | | | 3) PROVIDE SYSTEM SPECIFICATION SHEET | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 |
|