2010-07-14 18:39:26****PROVISO****
 ****SUBMIT CORRECTED INSTALLATION SCHEDULE AS A
 REVISION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SPANS NOT CORRECT; THIS SHOULD BE BLADE LENGTH. IF
 AN OPENING IS 101", 2" EDGE DISTANCE, WALL MOUNT TOP
 AND BOTTOM, SPAN SHOULD BE 102" MINIMUM.
  
 2. 2 1/2" SHUTTER TO GLASS SEPARATION PROPOSED, SEE
 PAGE 5, 2 7/8" REQUIRED FOR SPANS TO 8' FOR THE DP
 PROPOSED, SEE OTHER SPANS. 2 1/2" DOES NOT COMPLY FOR
 THIS DESIGN PRESSURE.
  
 3. TWO SETS REQUIRED; WHEN SUBMITTING THE REVISION,
 PLEASE PROVIDE TWO IDENTICAL SETS.
  
 4. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH THE ANCHOR SCHEDULES ON PAGE 6, C1 THROUGH C5 ARE
 THE MOUNTING TYPES FOR THIS PRODUCT APPROVAL, PLEASE
 REVISE INSTALLATION SCHEDULE.
  
 5. ANCHOR SPACING PROPOSED DOES NOT COMPLY FOR ANY OF
 THE SHUTTER CONNECTION MOUNTING TYPES. FOR INSTANCE,
 SEE OPENING 1. 3", 4", AND 9" ARE THE ANCHOR SPACINGS
 FOR ALLOWABLE MOUNTING TYPES FOR THIS DESIGN PRESSURE,
 BUT 10" IS PROPOSED. PLEASE SPECIFY SHUTTER CONNECTION
 MOUNTING TYPE AND REVISE ANCHOR SPACING TO COMPLY WITH
 REQUIREMENTS OF THE PRODUCT APPROVAL.
  
  