| 2010-07-14 18:39:26 | ****PROVISO**** |
| | ****SUBMIT CORRECTED INSTALLATION SCHEDULE AS A |
| | REVISION**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. SPANS NOT CORRECT; THIS SHOULD BE BLADE LENGTH. IF |
| | AN OPENING IS 101", 2" EDGE DISTANCE, WALL MOUNT TOP |
| | AND BOTTOM, SPAN SHOULD BE 102" MINIMUM. |
| | |
| | 2. 2 1/2" SHUTTER TO GLASS SEPARATION PROPOSED, SEE |
| | PAGE 5, 2 7/8" REQUIRED FOR SPANS TO 8' FOR THE DP |
| | PROPOSED, SEE OTHER SPANS. 2 1/2" DOES NOT COMPLY FOR |
| | THIS DESIGN PRESSURE. |
| | |
| | 3. TWO SETS REQUIRED; WHEN SUBMITTING THE REVISION, |
| | PLEASE PROVIDE TWO IDENTICAL SETS. |
| | |
| | 4. SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE |
| | WITH THE ANCHOR SCHEDULES ON PAGE 6, C1 THROUGH C5 ARE |
| | THE MOUNTING TYPES FOR THIS PRODUCT APPROVAL, PLEASE |
| | REVISE INSTALLATION SCHEDULE. |
| | |
| | 5. ANCHOR SPACING PROPOSED DOES NOT COMPLY FOR ANY OF |
| | THE SHUTTER CONNECTION MOUNTING TYPES. FOR INSTANCE, |
| | SEE OPENING 1. 3", 4", AND 9" ARE THE ANCHOR SPACINGS |
| | FOR ALLOWABLE MOUNTING TYPES FOR THIS DESIGN PRESSURE, |
| | BUT 10" IS PROPOSED. PLEASE SPECIFY SHUTTER CONNECTION |
| | MOUNTING TYPE AND REVISE ANCHOR SPACING TO COMPLY WITH |
| | REQUIREMENTS OF THE PRODUCT APPROVAL. |
| | |
| | |