Plan Review Notes For Permit 10070211
Permit Number 10070211
Review Stop E
Sequence Number 1
Notes
Date Text
2010-07-21 12:04:39REVISION REQUIRED
  
 SHEET E3.01 PANEL SCHEDULE P210. SECTION 2 DOES NOT
 CORRELATE WITH THE RISER FEEDER SIZES TO PANEL P210 A.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  