Date Text
2010-07-14 17:11:43****PROVISO****
 ****REVISION REQUIRED****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SUBSTRATE STATED ON INSTALLATION SCHEDULE IS
 MASONRY, ANCHOR SPACING DOES NOT COMPLY FOR CONCRETE
 BLOCK. ONLY ONE SUBSTRATE IS SPECIFIED (MASONRY); WHY
 ARE THERE TWO DIFFERENT ANCHOR SPACINGS FOR TOP AND
 BOTTOM FOR THE SAME MOUNTING CONNECTION TYPE (C2) AND
 SUBSTRATE (MASONRY)?
  
 PLEASE REVISE INSTALLATION SCHEDULE SO THAT
 INSTALLATION COMPLIES WITH PRODUCT APPROVAL. PLEASE
 CONTACT ME IF YOU NEED ASSISTANCE.
  