| Plan Review Notes For Permit 10070196 |
| Permit Number |
10070196 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-03 12:26:50 | *****REVIEW COMMENTS - FIRE***** | | | | | | 1) PROVIDE SUITE NUMBER IN TITLE BLOCK INFORMATION. | | | | | | 2) PROVIDE MINIMUM 6" TALL ADDRESS SUITE NUMBER ON | | | BUILDING. | | | | | | 3) ALL DEMOLITION WORK SHALL COMPLY WITH NFPA 241. | | | | | | 4) ALL NEW WORK SHALL COMPLY WITH THE FLORIDA FIRE | | | PREVENTION CODE, 2007 EDITION. | | | | | | 5) SHEET A-1: "EXISTING/DEMO PLAN PLAN" DOES NOT APPEAR | | | TO BE SCALED AT 1/4"=1'-0". | | | | | | 6) SHEET A-2: PROVIDE PORTABLE FIRE EXTINGUISHERS PER | | | NFPA 10. | | | | | | 7) SHEET A-2: AUTOMOTIVE SERVICE AND REPAIR CLASSIFIES | | | AS AN INDUSTRIAL OCCUPANCY, NOT A BUSINESS OCCUPANCY. | | | | | | 8) SHEET A-2: PROVIDE EXIT SIGNAGE AND EMERGENCY | | | LIGHTING FOR SMALL CORRIDOR ADJACENT TO RESTROOM. | | | | | | 9) SHEET A-2: EXISTING RESTROOM DOOR SWING OBSTRUCTS | | | EGRESS FROM NEWLY FORMED CORRIDOR (NFPA 101, 2007 ED, | | | SECTION 7.2.1.4.4). | | | | | | 10) SHEET A-2: DOOR LOCKS SHALL BE OPERABLE FROM THE | | | EGRESS SIDE AND SHALL NOT REQUIRE THE USE OF A KEY, | | | TOOL, OR SPECIAL KNOWLEDGE TO OPEN. | | | | | | 11) SHEET A-2: ADDITIONAL FIRE SPRINKLERS WILL BE | | | REQUIRED BELOW THE NEW GARAGE DOOR. SEPARATE PLANS AND | | | PERMIT REQUIRED FOR FIRE SPRINKLER WORK. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | WPB FIRE PLAN REVIEW | | | 561-805-6730 |
|