2010-08-03 12:26:50*****REVIEW COMMENTS - FIRE*****
  
 1) PROVIDE SUITE NUMBER IN TITLE BLOCK INFORMATION.
  
 2) PROVIDE MINIMUM 6" TALL ADDRESS SUITE NUMBER ON
 BUILDING.
  
 3) ALL DEMOLITION WORK SHALL COMPLY WITH NFPA 241.
  
 4) ALL NEW WORK SHALL COMPLY WITH THE FLORIDA FIRE
 PREVENTION CODE, 2007 EDITION.
  
 5) SHEET A-1: "EXISTING/DEMO PLAN PLAN" DOES NOT APPEAR
 TO BE SCALED AT 1/4"=1'-0".
  
 6) SHEET A-2: PROVIDE PORTABLE FIRE EXTINGUISHERS PER
 NFPA 10.
  
 7) SHEET A-2: AUTOMOTIVE SERVICE AND REPAIR CLASSIFIES
 AS AN INDUSTRIAL OCCUPANCY, NOT A BUSINESS OCCUPANCY.
  
 8) SHEET A-2: PROVIDE EXIT SIGNAGE AND EMERGENCY
 LIGHTING FOR SMALL CORRIDOR ADJACENT TO RESTROOM.
  
 9) SHEET A-2: EXISTING RESTROOM DOOR SWING OBSTRUCTS
 EGRESS FROM NEWLY FORMED CORRIDOR (NFPA 101, 2007 ED,
 SECTION 7.2.1.4.4).
  
 10) SHEET A-2: DOOR LOCKS SHALL BE OPERABLE FROM THE
 EGRESS SIDE AND SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, OR SPECIAL KNOWLEDGE TO OPEN.
  
 11) SHEET A-2: ADDITIONAL FIRE SPRINKLERS WILL BE
 REQUIRED BELOW THE NEW GARAGE DOOR. SEPARATE PLANS AND
 PERMIT REQUIRED FOR FIRE SPRINKLER WORK.
  