| Plan Review Notes For Permit 10070176 |
| Permit Number |
10070176 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-04 10:31:38 | BUILDING #6 - 8 UNIT TOWNHOUSES | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE RETURN AIR TRANSFER DUCT FROM THE MASTER BEDROOM | | | SUITE IS UNDER SIZED. FBC R M1602.4 REQUIRES THE | | | TRANSFER DUCT TO BE 1.5 TIMES THE SUPPLY, THEREFORE A | | | 14" DUCT IS REQUIRED. | | | PLEASE CORRECT. | | | | | | 2) THE EQUIPMENT MODEL NUMBERS ON THE PLANS AND THE | | | SIZING CALCS. DO NOT MATCH FOR THE END UNITS. PLEASE | | | CORRECT. | | | | | | 3) THE CU MOUNTING DETAIL ON THE MECHANICAL PLANS | | | REFERENCES THE 2004 FBC AND ASCE 02. PLEASE UPDATE TO | | | 2007 FBC AND ASCE7-05 AND CORRECT THE SECTIONS THAT ARE | | | LISTED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|