| 2010-07-28 11:08:34 | OAKTON PRESERVE |
| | PERMIT NUMBER 10070137 |
| | LOTS35,36,37,38,39,40,41, AND 42 |
| | |
| | 1. PER FLORIDA STATUE 553.885, THE CARBON MONOXIDE |
| | DETECTORS SHOWN ON THE SECOND FLOORS MUST BE INSTALLED |
| | WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| | |
| | 2. PER FLORIDA STATUE 633.027 "THE OWNER OF ANY |
| | COMMERCIAL OR INDUSTRIAL STRUCTURE, OR ANY MULT-UNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE, THAT USES |
| | LIGHT-FRAME TRUSS CONSTRUCTION SHALL MARK THE STRUCTURE |
| | WITH A SIGN APPROVED BY THE STATE FIRE MARSHAL IN A |
| | MANNER SUFFICIENT TO WARN PERSONS CONDUCTING FIRE |
| | CONTROL AND OTHER EMERGENCY OPERATIONS OF THE EXISTENCE |
| | OF LIGHT FRAME TRUSS TYPE CONSTRUCTION IN THE |
| | STRUCTURE". |
| | |
| | 3. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY |
| | WITH NFPA 241. |
| | |
| | 4. THE EGRESS WINDOW FOR BEDROOM 2 NOT IDENTIFIED ON |
| | PAGE TU-2.1. |
| | |
| | 5. PLEASE INDICATE INTERIOR FINISH CLASSIFICATION FOR |
| | WALLS AND CEILINGS IN EACH UNIT. |
| | |
| | 6. UNITS 35-36 ON PAGE A-3.1. HAVE NO PREMISES |
| | IDENTIFICATION. |
| | |
| | 7. PORTABLE FIRE EXTINGUISHERS NOT SHOWN? |
| | |
| | 8. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT |
| | LEAST 10 FEET FROM AIR CONDITIONER DIFUSERS. |
| | |
| | 9. PROVIDE DETAILS ON FIRE RETARDANT COATINGS DESCRIBED |
| | ON PAGES A-4.1 AND A-4.2. |
| | |
| | 10. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR HANDRAILS AND GUARDRAILS. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |