| 2010-07-14 13:41:20 | BUILDING PLAN REVIEW |
| | PERMIT: 10070135 |
| | ADD: 425 25TH ST |
| | CONT: CRL CONSTRUCTION INC |
| | TEL: (561)248-7177 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) DOORS 2, 5& 6ARE BEING REPLACED ENACTING 2007 |
| | EXISTING BUILDING CODE 706.1 A BUILDING, FACILITY OR |
| | ELEMENT THAT IS ALTERED SHALL COMPLY WITH CHAPTER 11 OF |
| | THE FLORIDA BUILDING CODE- BUILDING. |
| | |
| | 11-4.13.5 CLEAR WIDTH. DOORWAYS SHALL HAVE A MINIMUM |
| | CLEAR OPENING OF 32 INCHES (813 MM) WITH THE DOOR OPEN |
| | 90 DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND |
| | THE OPPOSITE STOP [SEE FIGURE 24(A), FIGURE 24(B), |
| | FIGURE 24(C), AND FIGURE 24(D)]. OPENINGS MORE THAN 24 |
| | INCHES (610 MM) IN DEPTH SHALL COMPLY WITH SECTIONS |
| | 11-4.2.1 AND 11-4.3.3 [SEE FIGURE 24(E)]. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |