| 2010-07-23 13:03:12 | *****DENIED***** | | | | | | 1) PROVIDE ADDRESS IN TITLEBLOCK. | | | 2) SPRINKLER IN NORTHEAST CORNER OF DINING AREA IS | | | LOCATED MORE THAN 7???-6??? FROM EAST WALL. | | | 3) TWO DINING AREA SPRINKLERS LOCATED IN THE 10???-0??? | | | CEILING HAVE SPRAY OBSTRUCTED BY A 9???-0??? SOFFIT. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 |
|