Plan Review Notes
Plan Review Notes For Permit 10070030
Permit Number 10070030
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-07-07 12:22:48300 EXECUTIVE CENTER DRIVE
 TENANT BUILD-OUT FOR NEW DIALYSIS CLINIC- FIRE ALARM
 PERMIT NUMBER 10070030
  
  
 1. WATERFLOW SWITCH SHALL ACTIVATE A WATERFLOW ALARM
 NOT A GENERAL ALARM AS IDENTIFIED AS ITEM # 5.
  
 2. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 3. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN
 ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE.
  
 4. INSTALLATION SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
 5. DUCT DETECTOR WHEN ACTIVATED SHALL CAUSE A GENERAL
 ALARM SIGNAL.
  
 6. WHEN COMPLETED, THE ENTIRE FIRE ALARM SYSTEM IS TO
 BE TESTED WITH REPRESENTATIVES OF THIS OFFICE.
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION