| Plan Review Notes For Permit 10070030 |
| Permit Number |
10070030 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-07 12:22:48 | 300 EXECUTIVE CENTER DRIVE | | | TENANT BUILD-OUT FOR NEW DIALYSIS CLINIC- FIRE ALARM | | | PERMIT NUMBER 10070030 | | | | | | | | | 1. WATERFLOW SWITCH SHALL ACTIVATE A WATERFLOW ALARM | | | NOT A GENERAL ALARM AS IDENTIFIED AS ITEM # 5. | | | | | | 2. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT | | | LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. | | | | | | 3. THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN | | | ACCORDANCE WITH NFPA 72, THE NATIONAL FIRE ALARM CODE. | | | | | | 4. INSTALLATION SUBJECT TO FIELD INSPECTION AND | | | APPROVAL. | | | | | | 5. DUCT DETECTOR WHEN ACTIVATED SHALL CAUSE A GENERAL | | | ALARM SIGNAL. | | | | | | 6. WHEN COMPLETED, THE ENTIRE FIRE ALARM SYSTEM IS TO | | | BE TESTED WITH REPRESENTATIVES OF THIS OFFICE. | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|