2010-12-29 11:22:271009 BANYAN BOULEVARD
 PERMIT NUMBER 10060914
 "CONTROL SYSTEM UPGRADE TO WATER TREATMENT PLANT"
  
  
 1. ADDRESS OF PROJECT NOT LISTED ON TITLE BLOCKS FOR
 THE PLAN SHEETS.
  
 2. PLEASE PROVIDE APPLICABLE BUILDING, ELECTRICAL, AND
 FIRE CODE STANDARDS TO PLAN SHEETS.
  
 3. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO
 COMPLY WITH NFPA 241.
  
 4. PLEASE INDICATE ON THE DRAWINGS THAT ALL ELECTRICAL
 WORK IS TO COMPLY WITH NFPA 70, THE NATIONAL ELECTRIC
 CODE.
  
 5. ARE ANY OF THE INSTRUMENTATION ON STAND-BY OR
 EMERGENCY POWER SYSTEMS.
  
 6. A SCOPE OF WORK NEEDS TO BE PROVIDED ON THE TITLE
 SHEET TO CLEARLY IDENTIFY THE TYPE AND AMOUNT OF WORK
 THAT IS TO BE PERFORMED. IN ADDITION, PLEASE EXPLAIN
 EXISTING AND NEW INTERFACE ISSUES REGARDING THE SCOPE
 OF WORK.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION