| Plan Review Notes For Permit 10060900 |
| Permit Number |
10060900 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-23 13:24:11 | *****DENIED***** | | | | | | 1) THE 2,526 SQ.FT. BUILDING EXTENSION WOULD QUALIFY AS | | | AN ADDITION AND NOT A LEVEL 3 ALTERATION. | | | 2) THE OCCUPANT LOAD FACTOR FOR THE NEW ADDITION SHALL | | | BE BASED UPON 7 SQ.FT. PER PERSON AS THE SEATING IS | | | LABELED AS ???REMOVABLE CHAIRS.??? THIS CHANGE WILL | | | RESULT IN AN OCCUPANT LOAD OF 346 PERSONS. | | | 3) AN AUTOMATIC FIRE SPRINKLER SYSTEM IS REQUIRED FOR | | | NEW ASSEMBLY OCCUPANCIES OVER 300 PERSONS. | | | 4) THE EXISTING ASSEMBLY OCCUPANCY IS NOT SPRINKLED; | | | THE BUILDING ADDITION WOULD CREATE NONCONFORMITY WITH | | | REGARDS TO FIRE PROTECTION, SO THE EXISTING BUILDING | | | WOULD REQUIRE AUTOMATIC SPRINKLER PROTECTION. | | | 5) ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OVER 300 | | | REQUIRES A FIRE ALARM SYSTEM WITH VOICE EVACUATION. | | | DRAWINGS SHOW HORN/STROBE DEVICES, THESE DEVICES WOULD | | | NEED TO BE SPEAKER/STROBE NOTIFICATION DEVICES. | | | 6) ACTIVITIES ROOM AND MULTI-PURPOSE ROOMS ARE PUBLIC | | | SPACES REQUIRING VISUAL FIRE ALARM NOTIFICATION | | | DEVICES. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | & WESLEY JOLIN | | | FIRE PLAN REVIEW | | | 561-805-6730 | | | |
|