2010-07-23 13:24:11*****DENIED*****
  
 1) THE 2,526 SQ.FT. BUILDING EXTENSION WOULD QUALIFY AS
 AN ADDITION AND NOT A LEVEL 3 ALTERATION.
 2) THE OCCUPANT LOAD FACTOR FOR THE NEW ADDITION SHALL
 BE BASED UPON 7 SQ.FT. PER PERSON AS THE SEATING IS
 LABELED AS ???REMOVABLE CHAIRS.??? THIS CHANGE WILL
 RESULT IN AN OCCUPANT LOAD OF 346 PERSONS.
 3) AN AUTOMATIC FIRE SPRINKLER SYSTEM IS REQUIRED FOR
 NEW ASSEMBLY OCCUPANCIES OVER 300 PERSONS.
 4) THE EXISTING ASSEMBLY OCCUPANCY IS NOT SPRINKLED;
 THE BUILDING ADDITION WOULD CREATE NONCONFORMITY WITH
 REGARDS TO FIRE PROTECTION, SO THE EXISTING BUILDING
 WOULD REQUIRE AUTOMATIC SPRINKLER PROTECTION.
 5) ASSEMBLY OCCUPANCY WITH AN OCCUPANT LOAD OVER 300
 REQUIRES A FIRE ALARM SYSTEM WITH VOICE EVACUATION.
 DRAWINGS SHOW HORN/STROBE DEVICES, THESE DEVICES WOULD
 NEED TO BE SPEAKER/STROBE NOTIFICATION DEVICES.
 6) ACTIVITIES ROOM AND MULTI-PURPOSE ROOMS ARE PUBLIC
 SPACES REQUIRING VISUAL FIRE ALARM NOTIFICATION
 DEVICES.
  
 MIKE CARSILLO, BATTALION CHIEF
 & WESLEY JOLIN
 FIRE PLAN REVIEW
 561-805-6730
  