| Plan Review Notes For Permit 10060900 |
| Permit Number |
10060900 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-11 15:23:29 | 1. NEW SUB PANEL R-H LOCATION NOT SHOWN ON PLAN, FBC | | | 106 | | | | | | 2. LOAD CALCULATIONS INCORRECT, NEC240.42 | | | | | | 3. A/C LOAD TO BE AS PER NEC 220.14A | | | | | | 4. RISER DIAGRAM INCORRECT, PLEASE PROVIDE MORE DETAIL | | | | | | 5. HOW IS NEW PANEL RH BEING FED, PLEASE SHOW ON PLAN | | | | | | | | | | | | JOHN DICKINSON (CONTRACT REVIEWER) | | | PX3182 | | | 561-718-3230 | | | 561-805-6650 | | | | | | | | | | | | |
|