Plan Review Notes
Plan Review Notes For Permit 10060900
Permit Number 10060900
Review Stop B
Sequence Number 1
Notes
Date Text
2010-07-06 16:58:06BUILDING PLAN REVIEW
 PERMIT: 10060900
 ADD: 540 CHEERFUL STREET
 CONT: WINGATE CORP
 TEL: (561)718-5133
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 SHEET A-2
 BUILDING CODE ANALYSIS
 BUILDING TYPE 2-B NON-SPRINKLERED WITH ADDITION 6,438
 SQ FT
 OCCUPANCY A3
  
  
 1) SHEET A-1:
  
 1A) EXISTING NOTE EN #19, INDICATES THE REMOVAL OF
 BLOCK WALLS WHICH APPEAR TO BE EXTERIOR BEARING WALLS
 WITH NO ADDITIONAL STRUCTURAL SUPPORT OF THE EXISTING
 BEAMS. THERE WILL BE A ADDITIONAL ROOF LOADING WITH THE
 NEW PIGGYBACK TRUSSES AND ROOF ASSEMBLY BEING ADDED TO
 THIS AREA. SHEET S-1 INDICATES NEW LVL BEAM AND BRACKET
 ATTACHMENT WITH FILLET WELDS BUT NOT SIZED FOR BUCKET
 ATTACHMENT TO PN39 NOR THE TUBULAR STEEL BRACING PN55.
  
 1B) EXISTING NOTE EN #17, INDICATES THE REMOVAL OF
 WINDOWS IN THE EXISTING EXTERIOR WALL AND
 REINSTALLATION IN THE NEW EXTERIOR WALLS OF THE
 ADDITION. TO REUSE THESE WINDOWS WITHIN THE ADDITION
 THEY MUST MEET THE STANDARD FOR NEW CONSTRUCTION IN THE
 FBC-B. FLORIDA EXISTING BUILDING CODE 1003.1 COMPLIANCE
 WITH THE FLORIDA BUILDING CODE. ADDITIONS TO EXISTING
 BUILDINGS OR STRUCTURES ARE NEW CONSTRUCTION AND SHALL
 COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING.
 PROVIDE DOCUMENTATION FOR LARGE MISSILE IMPACT
 RESISTANT TESTING FBC-B 1609.1.2 AND FOR
 FBC-B 1714.5.1. DESIGN PRESSURES.
  
 1C) UNITY OF TITLE. THE PROPOSED BUILDING STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES BETWEEN THE LOTS
 WHICH COMBINE TO FORM 'THE SITE'. A 'UNITY OF TITLE'
 SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE. THE ADDITION CROSSES LOT-LINE #19 & 23.3.
 REVIEW AT PALM BEACH COUNTY PROPERTY APPRAISERS WEB
 SITE: WWW.PBCGOV.COM/PAPA
  
 2) SHEET A-2:
  
 2A) THE BUILDING CODE ANALYSIS INDICATES THE EXISTING
 BUILDING AND ADDITION ARE TO BE A BUILDING TYPE II-B.
 PLEASE CHECK TO BE IF THE EXISTING BUILDINGS ROOF
 FRAMING (TRUSSES) AND ROOF SHEATHING ARE FIRE RETARDANT
 TREATED WOOD. I HAVEN???T SEEN TRUSSES MADE OF FIRE
 RETARDANT TREATED WOOD SINCE THE FIRE RETARDANT SALT
 IMPREGNATED INTO THE WOOD ARE CORROSIVE AND WILL EAT
 THE TINY TEETH OF THE TRUSS PLATES. PLEASE REVIEW FBC-B
 603.1 (1.3) FOR BOTH THE EXISTING BUILDING AND
 ADDITION!
  
 2B) THE EXISTING MULTIPURPOSE ROOM INDICATES AN
 OCCUPANCY LOAD BASED ON 7 SQ FT/ PER PERSON WITH
 REMOVABLE CHAIRS, IN THE NEW ADDITION (MULTIPURPOSE
 ROOM) THE OCCUPANCY LOAD IS BASED ON 15 SQ FT/ PER
 PERSON. SINCE THE NEW ADDITION IS ALSO A MULTIPURPOSE
 ROOM ARE THESE CHAIRS FIXED OR REMOVABLE. THE OCCUPANT
 LOAD WILL BE CONSIDERED AT 7 SQ FT /PER PERSON IF
 REMOVABLE? TABLE 1004.1.1.
  
 2C) IN THE NEW MULTIPURPOSE ROOM ON THE EAST SIDE THERE
 IS A NOTE FOR EGRESS DOORS BUT THE PICTORIAL IS
 MISSING, 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 2D) 2007 EXISTING BUILDING CODE,
 1001.1 SCOPE. AN ADDITION TO A BUILDING OR STRUCTURE
 SHALL COMPLY WITH THE FLORIDA BUILDING CODE AS ADOPTED
 FOR NEW CONSTRUCTION WITHOUT REQUIRING THE EXISTING
 BUILDING OR STRUCTURE TO COMPLY WITH ANY REQUIREMENTS
 OF THOSE CODES OR OF THESE PROVISIONS, EXCEPT AS
 REQUIRED BY THIS CHAPTER. WHERE AN ADDITION IMPACTS THE
 EXISTING BUILDING OR STRUCTURE, THAT PORTION SHALL
 COMPLY WITH THIS CODE.
  
 1001.2 CREATION OR EXTENSION OF NONCONFORMITY. AN
 ADDITION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY
 IN THE EXISTING BUILDING TO WHICH THE ADDITION IS BEING
 MADE WITH REGARD TO ACCESSIBILITY, STRUCTURAL STRENGTH,
 FIRE SAFETY, MEANS OF EGRESS, OR THE CAPACITY OF
 MECHANICAL, PLUMBING, OR ELECTRICAL SYSTEMS.
  
 THE ADDITION AND REMOVAL OF WALL CREATES ONE LARGE ROOM
 OR FIRE AREA, IT IS NO LONGER TWO SEPARATE ROOM. THIS
 CREATES A NONCONFORMITY. 2007 FBC-B 903.2.1.3 A-3(2)
 THE FIRE AREA HAS AN OCCUPANT LOAD OF 300 OR MORE. SEE
 DEFINITIONS 702 FIRE AREA. THE AGGREGATE FLOOR AREA
 ENCLOSED AND BOUNDED BY FIRE WALLS, FIRE BARRIERS,
 EXTERIOR WALLS OR FIRE-RESISTANCE RATED HORIZONTAL
 ASSEMBLIES OF A BUILDING.
  
 3) SHEET A-3:
  
 3A) NOTE PN-6 INDICATES NEW EXTERIOR DOORS, AND NOTE
 PN-7 THE REUSE OF EXISTING WINDOWS, SHEET S-2
 STRUCTURAL SPECIFICATION INDICATES WITH NOTE 6
 COMPONENTS AND CLADDING WIND PRESSURES ???SEE TABLE,
 WHERE? 1609.1.1 / ASCE 7-05.
  
 3B) WIND DESIGN FOUND ON S-2 NOTE #6 WIND DESIGN
 CRITERIA, THE DESIGNER CAN DESIGN TO A HIGHER WIND
 SPEED AS INDICATED ON PLANS TO 155 MPH BUT THE EXPOSURE
 FACTOR ???B??? NEEDS TO BE CONSIDERED A ???C??? ZONE
 WHICH WILL HAVE HIGHER MULTIPLIERS FOR THE COMPONENTS
 AND CLADDING. PLEASE REVIEW 1609.4.3
 OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS, INCLUDING
 SURFACE UNDULATIONS OR OTHER IRREGULARITIES, HAVING
 HEIGHTS GENERALLY LESS THAN 30 FEET (9144 MM) EXTENDING
 MORE THAN 1,500 FEET (457.2 M) FROM THE BUILDING SITE
 IN ANY QUADRANT. THIS EXPOSURE SHALL ALSO APPLY TO ANY
 BUILDING LOCATED WITHIN EXPOSURE B-TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF EXPOSURE C-TYPE TERRAIN THAT
 EXTENDS MORE THAN 600 FEET (182.9 M) AND WIDTH GREATER
 THAN 150 FT. IN THE UPWIND DIRECTION.
  
 3C) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 3C) (1) WINDOWS
 3C) (2) EXTERIOR DOORS
 3C) (3) LINTELS
 3C) (4) WALL LOUVER A/C MAKE UP AIR
 3C) (5) ROOFING ASSEMBLIES
  
 3D) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved