| Plan Review Notes For Permit 10060876 |
| Permit Number |
10060876 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-26 11:04:48 | "INSTALLING TWO CARD READERS AT NEW GATE ADDRESS" | | | PERMIT REVISION TRACKING NUMBER 10060876 | | | | | | 1. ON PAGE SE-01 DRAWINGS INDICATE "CARD READER IN" AND | | | A "CARD READER OUT" AT THE GATE LOCATIONS. NO | | | INFORMATION PROVIDED ON FIRE AND PARAMEDICAL ACCESS | | | THROUGH THESE GATES. KNOX BOX KEY SWITCHES ARE REQUIRED | | | TO ACCESS THE GATES. PLEASE GO TO WWW.KNOXBOX.COM TO | | | ORDER KEY SWITCHES FOR USE BY THE FIRE RESCUE | | | DEPARTMENT. IN ADDIITION HOW DO THE GATES OPERATE IN | | | THE EVENT OF LOSS OF POWER? DO THE GATES REMAIN FAIL | | | SAFE OR FAIL SECURE? PLEASE PROVIDE INFORMATION ON THE | | | PLANS. | | | | | | 2. THE SPECIAL LOCKING ARRANGEMENTS DISPLAYED ON PAGE | | | SE-03 SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION | | | CODE (FFPC). THESE SPECIAL LOCKING ARRANGEMENTS MUST BE | | | TESTED TO ENSURE PROPER OPERATION. | | | | | | 3. TITLE BLOCK CONTAINS A DIFFERENT ADDRESS THAN WHAT | | | IS LISTED ON PLAN/PERMIT REVISION FORM SUBMITTED TO THE | | | CONSTRUCTION SERVICES DEPARTMENT. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|