2010-08-16 18:09:53****PROVISO****
 ****REVISION REQUIRED PRIOR TO FIRST INSPECTION****
 ****ISSUED AT CONTRACTOR'S RISK****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE SUBMIT TWO SETS OF THE CORRECTED INSTALLATION
 SCHEDULE, SEE FOLLOWING COMMENTS.
  
 2. NEW DESIGN PRESSURES WERE SUBMITTED FOR EXP C BUT
 THE INSTALLATION SCHEDULE WAS NOT REVISED TO IMPLEMENT
 CORRECT PRESSURES. ANCHOR SPACING DOES NOT COMPLY, SEE
 NOA.
  
 3. INSTALLATION SCHEDULE STATES SUBSTRATE IS "C/B",
 WHAT DOES THIS MEAN? CONCRETE BLOCK, TOP AND BOTTOM?
 CONCRETE TOP, BLOCK BOTTOM? ANCHOR SPACING DOES NOT
 COMPLY FOR BLOCK SUBSTRATE, PLEASE SEE NOA.
  
  
  
  
  