| Plan Review Notes For Permit 10060834 |
| Permit Number |
10060834 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-07 10:41:51 | PHASE II BULK CHLORINE STORAGE BUILDING REMODEL | | | PERMIT NUMBER 10060834 | | | | | | 1. PROPER CARE AND SAFEQUARDS REQUIRED DURING | | | EXCAVATION ACTIVITIES. | | | | | | 2. ALL NEW STORAGE TANKS ARE TO BE PROPERLY LABELED | | | WITH TANK CONTENTS, QUANTITIES, AND NFPA 704 DIAMONDS. | | | | | | 3. EXTREME CARE IS TO BE TAKEN WHEN THE EXISTING | | | CHLORINE CYLINDERS ARE REMOVED. | | | | | | 4. DEMOLITION, RENOVATION, AND CONSTRUCTION TO COMPLY | | | WITH NFPA 241. | | | | | | 5. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | SYSTEM REMODEL OR INSTALLATION. | | | | | | 6. ALL CONTROL VALVES ARE TO BE PROPERLY IDENTIFIED. | | | | | | 7. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | | NATIONAL ELECTRIC CODE. | | | | | | 8. ENSURE THAT EXITS ARE PROPERLY IDENTIFIED. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | |
|