Plan Review Notes
Plan Review Notes For Permit 10060823
Permit Number 10060823
Review Stop B
Sequence Number 3
Notes
Date Text
2010-10-14 12:40:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 THIRD REVIEW, SAME PLANS SUBMITTED AS #2 EXCEPT PLANS
 ARE FULL SIZE AND SIGNED & SEALED
  
 COMMENTS REMAIN THE SAME FROM PREVIOUS LIST FOR
 CONSISTENCY:
  
 1. FROM PREVIOUS REVIEW, PLEASE REVISE THE PLAN TO
 INCLUDE INFORMATION REGARDING THE ACCESSIBLE ROUTE AND
 THE ACCESSIBLE ENTRANCE(S). BASED ON INFORMATION
 PROVIDED REGARDING THE SITE, THE ACCESSIBLE SPACES
 SHOWN ARE NOT LOCATED ON THE SHORTEST ACCESSIBLE ROUTE,
 SEE FBC11-4.6.2.
  
 2ND REVIEW, BASED ON THE NEW INFORMATION PROVIDED, IT
 APPEARS THAT THE ACCESSIBLE PARKING IS LOCATED FARTHER
 FROM THE ACCESSIBLE ENTRANCE THAN OTHER SPACES. IT
 APPEARS THAT, RATHER THAN CREATE AN ACCESSIBLE ROUTE
 FROM FARTHER PARKING SPACES, THE ROUTE SHOULD BE
 CREATED FROM THE PARKING SPACES WHICH ARE CLOSEST TO
 THE ACCESSIBLE ENTRANCE.
  
 3RD REVIEW, SEE COMMENT FROM 2ND REVIEW. ALSO PLEASE
 NOTE THAT ONE OF THE PROPOSED ROUTE DIRECTS THE
 ACCESSIBLE ROUTE THROUGH TRAFFIC COMING IN OFF OF THE
 STREET. AS THIS IS A PARKING LOT, IT APPEARS THAT THE
 ACCESSIBLE ROUTE WILL CROSS TRAFFIC REGARDLESS OF
 LOCATION (AS IS TYPICAL OF MOST LARGE PARKING LOT
 CONFIGURATIONS). PLEASE SEE FBC11-4.6.2, ACCESSIBLE
 PARKING SPACES SHALL BE LOCATED ON THE SHORTEST SAFELY
 ACCESSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE.
  
 2. PLEASE PROVIDE DETAILS FOR THE RAMPS PROPOSED. NOTE
 THAT RAMPS ARE TO COMPLY WITH FBC11-4.7 (CURB RAMPS) OR
 FBC11-4.8 (RAMPS).
  
 2ND REVIEW, THE PLAN PROVIDED APPEARS TO BE AN 8 1/2" X
 11" REDUCED SHEET BASED ON A 24"X36" PLAN. IT IS VERY
 DIFFICULT TO READ. SOME NUMBERS ARE ENTIRELY ILLEGIBLE
 DUE TO THE VERY SMALL SIZE. PLEASE SUBMIT FULL SIZE
 PLANS. SEE FBC106, PLANS ARE TO BE LEGIBLE.
  
 A SP2, RAMP IS LABELED AS A CURB RAMP BUT NOT DRAWN AS
 SUCH, SEE FBC 11 FIGURE 12.
  
 SP2, SEE FBC 11 4.29.2 AND FIGURE 11 40. IT IS NOT
 CLEAR WHY THE DETECTABLE WARNING IN DETAIL A IS ON AN
 ANGLE, DETAIL B IS A SEMICIRCLE. A COMPLETE REVIEW OF
 THE DETAILS HAS NOT BEEN DONE AT THIS TIME PENDING A
 FULL SIZE DETAIL WITH LEGIBLE TEXT.
  
 3. SOME DETECTABLE WARNINGS ARE IN A SEMICIRCLE
 CONFIGURATION OR ON AN ANGLE, PLEASE CLARIFY. PLEASE
 SEE EXAMPLES NOTED IN 2ND REVIEW ITEM 2. ALSO SEE
 FBC11-4.7, REGARDING CURB RAMP DETECTABLE WARNINGS.
  
 4-5. ADDRESSED.
  
 6. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  
 NOT ADDRESSED; THIRD REQUEST. THE CONTRACT SHOULD
 INCLUDE A COST BREAKDOWN, FBC11-4.1.6(2).
  
 7. DETAIL 2 SP1, HANDICAP PARKING SIGN TO INCLUDE THE
 FINE AND THE 84" DIMENSION SHOULD BE FROM GRADE TO
 BOTTOM OF SIGN (DIMENSION APPEARS TO BE RELATED TO
 FOOTING), FBC11-4.6.4.
  
 8. (NEW COMMENT, THIRD REVIEW) - PLEASE NOTE THAT MOST
 ITEMS CAN BE PROVISO OR REDLINE ITEMS AFTER RESOLUTION
 OF THE LOCATION ISSUE.
  
  