| Plan Review Notes For Permit 10060819 |
| Permit Number |
10060819 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-07 15:02:55 | 1901 NORTH FLAGLER DRIVE | | | TEMPLE ISRAEL | | | PERMIT NUMBER 10060819 | | | FIRE SPRINKLER PLAN | | | | | | 1. CONSTRUCTION DOCUMENT SHEET FP-2 LABELS STORAGE # 2 | | | -205 AND MECHANICAL # 2-291 AS ORDINARY HAZARD GROUP II | | | AND A DENSITY .2 GPM PER SQUARE FOOT. PLEASE PROVIDE | | | HYDRAULIC CALCULATIONS. | | | | | | 2. STORAGE ROOM # 2-205 HAS A SPRINKLER IN THE NE | | | CORNER THAT IS CONNECTED TO ANY PIPE. | | | | | | 3. HYDRAULICALLY CALCULATED AREA IS LESS THAN 900 | | | SQUARE FEET. | | | | | | 4. FLEXHEAD DETAIL IS DIFFICULT TO READ. PLEASE PROVIDE | | | THE FOLLOWING INFORMATION ON THE DRAWING LENGTH OF | | | FLEXIBLE DROP, RADIUS OF FLEXIBLE CONNECTION, AND | | | MAXIMUM NUMBER OF BENDS. | | | | | | | | | DENIED | | | | | | | | | WESLEY JOLIN, FIRE PROTECTION ENGINEER | | | BUREAU OF FIRE PREVENTION | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|