Plan Review Notes
Plan Review Notes For Permit 10060790
Permit Number 10060790
Review Stop B
Sequence Number 1
Notes
Date Text
2010-07-07 16:30:43****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. EITHER SHOW HOW THIS STRUCTURAL EXTERIOR RENOVATION
 IS EXEMPT FROM ENGINEERING OR PROVIDE ENGINEERING FOR
 THIS IMPROVEMENT.
  
 2. PROVIDE A SITE PLAN SHOWING PROPOSED IMPROVEMENT AND
 DISTANCE TO PROPERTY LINE.
  
 3. BOND BREAK REQUIRED FBC1404.2.1.
  
 4. DECLARE BUILDING TYPE, FBC 5. IT APPEARS THAT YOU
 PROPOSE TO INSTALL COMBUSTIBLE MATERIAL IN A BUILDING
 WHICH CURRENTLY HAS NON COMBUSTIBLE EXTERIOR BEARING
 WALLS; DEMONSTRATE THAT THIS IS PERMITTED UNDER THE
 CODE.
  
 5. DECLARE WIND DESIGN CRITERIA FBC1603.1.4.
  
 6. PROVIDE A COMPLETE STRUCTURAL DETAIL FOR PROPOSED
 WORK. IT IS NOT CLEAR HOW THIS WILL RESIST WIND LOADS
 AS DETAIL WAS INCOMPLETE, ALL FASTENERS NOT SPECIFIED
 AND NO STRAPS SPECIFIED.
 FBC106, FBC 1609.
  
 7. PLEASE SHOW HOW THE REDUCED WIDTH WILL AFFECT
 EXITING, FBC CH. 10.
  
  