| Plan Review Notes For Permit 10060790 |
| Permit Number |
10060790 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-07-07 16:30:43 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. EITHER SHOW HOW THIS STRUCTURAL EXTERIOR RENOVATION | | | IS EXEMPT FROM ENGINEERING OR PROVIDE ENGINEERING FOR | | | THIS IMPROVEMENT. | | | | | | 2. PROVIDE A SITE PLAN SHOWING PROPOSED IMPROVEMENT AND | | | DISTANCE TO PROPERTY LINE. | | | | | | 3. BOND BREAK REQUIRED FBC1404.2.1. | | | | | | 4. DECLARE BUILDING TYPE, FBC 5. IT APPEARS THAT YOU | | | PROPOSE TO INSTALL COMBUSTIBLE MATERIAL IN A BUILDING | | | WHICH CURRENTLY HAS NON COMBUSTIBLE EXTERIOR BEARING | | | WALLS; DEMONSTRATE THAT THIS IS PERMITTED UNDER THE | | | CODE. | | | | | | 5. DECLARE WIND DESIGN CRITERIA FBC1603.1.4. | | | | | | 6. PROVIDE A COMPLETE STRUCTURAL DETAIL FOR PROPOSED | | | WORK. IT IS NOT CLEAR HOW THIS WILL RESIST WIND LOADS | | | AS DETAIL WAS INCOMPLETE, ALL FASTENERS NOT SPECIFIED | | | AND NO STRAPS SPECIFIED. | | | FBC106, FBC 1609. | | | | | | 7. PLEASE SHOW HOW THE REDUCED WIDTH WILL AFFECT | | | EXITING, FBC CH. 10. | | | | | | |
|