| 2010-06-30 15:22:02 | BUILDING PLAN REVIEW |
| | PERMIT: 10060679 |
| | ADD: 324 LYMAN PLACE |
| | CONT:TO BE DETERMINED |
| | CONTACT: TAYLOR, TRINETTA |
| | TEL: (561)719-9138 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 2007 EXISTING BUILDING CODE |
| | 901.3 CHANGE OF OCCUPANCY CLASSIFICATION. WHERE THE |
| | OCCUPANCY CLASSIFICATION OF A BUILDING CHANGES, THE |
| | PROVISIONS OF SECTIONS 902 THROUGH 912 SHALL APPLY. |
| | THIS INCLUDES A CHANGE OF OCCUPANCY CLASSIFICATION |
| | WITHIN A GROUP AS WELL AS A CHANGE OF OCCUPANCY |
| | CLASSIFICATION FROM ONE GROUP TO A DIFFERENT GROUP. |
| | |
| | 901.4 CERTIFICATE OF OCCUPANCY REQUIRED. A CERTIFICATE |
| | OF OCCUPANCY SHALL BE ISSUED WHERE A CHANGE OF |
| | OCCUPANCY OCCURS THAT RESULTS IN BEING CLASSIFIED AS A |
| | DIFFERENT OCCUPANCY CLASSIFICATION AS DETERMINED BY THE |
| | FLORIDA BUILDING CODE, BUILDING |
| | |
| | 1) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE |
| | OF OCCUPANCY: |
| | |
| | A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS |
| | DESIGNED. 2007 EXISTING BUILDING CODE- CHAPTER 9 CHANGE |
| | IN OCCUPANCY |
| | |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE |
| | PROVISIONS OF CHAPTER 3. |
| | |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 5, |
| | TABLE 503 FBC-BUILDING |
| | |
| | D) THE OCCUPANT LOAD, SEE TABLE1004.1.1. |
| | |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED? |
| | |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED |
| | |
| | 2) EXT BLD CODE 903.1 GENERAL. BUILDING ELEMENTS AND |
| | MATERIALS IN PORTIONS OF BUILDINGS UNDERGOING A CHANGE |
| | OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION |
| | 912. |
| | |
| | EXT BLD CODE 904.1 GENERAL. FIRE PROTECTION |
| | REQUIREMENTS OF SECTION 912 SHALL APPLY WHERE A |
| | BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE OF |
| | OCCUPANCY CLASSIFICATION. |
| | 912.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS |
| | SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 912.2.1 |
| | AND 912.2.2. |
| | |
| | EXT BLD CODE 912.2.1 FIRE SPRINKLER SYSTEM. WHERE A |
| | CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT REQUIRES |
| | AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED |
| | ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| | THE FLORIDA BUILDING CODE, BUILDING , SUCH SYSTEM SHALL |
| | BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| | OCCUPANCY OCCURS. |
| | |
| | FBC-BUILDING 903.3.1.4 IN GROUP R4 SMALL FACILITIES, AN |
| | AUTOMATED SPRINKLER SYSTEMS INSTALLED IN ACCORDANCE |
| | WITH NFPA 13D OR 13R WITH THEIR SCOPES SHALL BE |
| | PERMITTED, PROVIDED THE AUTOMATIC SPRINKLER SYSTEM IS |
| | NOT BE CONSIDERED AN ALTERNATIVE TO OTHER REQUIREMENTS |
| | OF THE CODE. |
| | |
| | 3) EXT BLD CODE 912.2.2 FIRE ALARM AND DETECTION |
| | SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION |
| | OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM |
| | TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE |
| | WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , |
| | SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE |
| | THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM |
| | NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY |
| | ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING |
| | IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM |
| | NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT |
| | THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL |
| | BE AUTOMATICALLY ACTIVATED. |
| | |
| | FBC-BUILDING 907.2.10.1.2 GROUPS R-2, R-3, R-4 AND I-1. |
| | SINGLE- OR MULTIPLE-STATION SMOKE ALARMS SHALL BE |
| | INSTALLED AND MAINTAINED IN GROUPS R-2, R-3, R-4 AND |
| | I-1, REGARDLESS OF OCCUPANT LOAD AT ALL OF THE |
| | FOLLOWING LOCATIONS: |
| | 3.1. ON THE CEILING OR WALL OUTSIDE OF EACH SEPARATE |
| | SLEEPING AREA IN THE IMMEDIATE VICINITY OF BEDROOMS. |
| | |
| | 3.2. IN EACH ROOM USED FOR SLEEPING PURPOSES. |
| | |
| | 3.3. IN EACH STORY WITHIN A DWELLING UNIT, INCLUDING |
| | BASEMENTS BUT NOT INCLUDING CRAWL SPACES AND |
| | UNINHABITABLE ATTICS. IN DWELLINGS OR DWELLING UNITS |
| | WITH SPLIT LEVELS AND WITHOUT AN INTERVENING DOOR |
| | BETWEEN THE ADJACENT LEVELS, A SMOKE ALARM INSTALLED ON |
| | THE UPPER LEVEL SHALL SUFFICE FOR THE ADJACENT LOWER |
| | LEVEL PROVIDED THAT THE LOWER LEVEL IS LESS THAN ONE |
| | FULL STORY BELOW THE UPPER LEVEL. |
| | |
| | 4)EXT BLD CODE 912.3 INTERIOR FINISH. IN AREAS OF THE |
| | BUILDING UNDERGOING THE CHANGE OF OCCUPANCY |
| | CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND |
| | CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY |
| | CLASSIFICATION. |
| | |
| | FBC-BUILDING 803.5 INTERIOR FINISH REQUIREMENTS BASED |
| | ON GROUP. INTERIOR WALL AND CEILING FINISH SHALL HAVE A |
| | FLAME SPREAD INDEX NOT GREATER THAN THAT SPECIFIED IN |
| | TABLE 803.5 FOR THE GROUP AND LOCATION DESIGNATED. |
| | INTERIOR WALL AND CEILING FINISH MATERIALS, OTHER THAN |
| | TEXTILES, TESTED IN ACCORDANCE WITH NFPA 286 AND |
| | MEETING THE ACCEPTANCE CRITERIA OF SECTION 803.2.1, |
| | SHALL BE PERMITTED TO BE USED WHERE A CLASS A |
| | CLASSIFICATION IN ACCORDANCE WITH ASTM E 84 IS |
| | REQUIRED. |
| | |
| | FBC-BUILDING 803.1 GENERAL. INTERIOR WALL AND CEILING |
| | FINISHES SHALL BE CLASSIFIED IN ACCORDANCE WITH ASTM E |
| | 84. SUCH INTERIOR FINISH MATERIALS SHALL BE GROUPED IN |
| | THE FOLLOWING CLASSES IN ACCORDANCE WITH THEIR FLAME |
| | SPREAD AND SMOKE-DEVELOPED INDEXES. |
| | |
| | CLASS A: FLAME SPREAD 0-25; SMOKE-DEVELOPED 0-450. |
| | |
| | CLASS B: FLAME SPREAD 26-75; SMOKE-DEVELOPED 0-450. |
| | |
| | CLASS C: FLAME SPREAD 76-200; SMOKE-DEVELOPED 0-450. |
| | |
| | 5) EXT BLD CODE 905.1 GENERAL. MEANS OF EGRESS IN |
| | PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH SECTION 912. |
| | |
| | EXT BLD CODE 912.4.1 MEANS OF EGRESS FOR CHANGE TO |
| | HIGHER HAZARD CATEGORY. WHEN A CHANGE OF OCCUPANCY |
| | GROUP IS MADE TO A HIGHER HAZARD CATEGORY (LOWER |
| | NUMBER) AS SHOWN IN TABLE 912.4, THE MEANS OF EGRESS |
| | SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTER 10 OF THE |
| | FLORIDA BUILDING CODE, BUILDING . |
| | |
| | |
| | FBC-BUILDING 1026.1 GENERAL. IN ADDITION TO THE MEANS |
| | OF EGRESS REQUIRED BY THIS CHAPTER, PROVISIONS SHALL BE |
| | MADE FOR EMERGENCY ESCAPE AND RESCUE IN GROUP R |
| | OCCUPANCY. BASEMENTS AND SLEEPING ROOMS BELOW THE |
| | FOURTH STORY ABOVE GRADE PLANE SHALL HAVE AT LEAST ONE |
| | EXTERIOR EMERGENCY ESCAPE AND RESCUE OPENING IN |
| | ACCORDANCE WITH THIS SECTION. WHERE BASEMENTS CONTAIN |
| | ONE OR MORE SLEEPING ROOMS, EMERGENCY EGRESS AND RESCUE |
| | OPENINGS SHALL BE REQUIRED IN EACH SLEEPING ROOM, BUT |
| | SHALL NOT BE REQUIRED IN ADJOINING AREAS OF THE |
| | BASEMENT. SUCH OPENINGS SHALL OPEN DIRECTLY INTO A |
| | PUBLIC WAY OR TO A YARD OR COURT THAT OPENS TO A PUBLIC |
| | WAY. THE EMERGENCY ESCAPE AND RESCUE OPENING SHALL BE |
| | PERMITTED TO OPEN INTO A SCREEN ENCLOSURE, OPEN TO THE |
| | ATMOSPHERE, WHERE A SCREEN DOOR IS PROVIDED LEADING |
| | AWAY FROM THE RESIDENCE. SUCH OPENING SHALL BE |
| | OPERATIONAL FROM THE INSIDE WITHOUT THE USE OF SPECIAL |
| | KNOWLEDGE, KEYS OR TOOLS. |
| | |
| | 1026.2 MINIMUM SIZE. EMERGENCY ESCAPE AND RESCUE |
| | OPENINGS SHALL HAVE A MINIMUM NET CLEAR OPENING OF 5.7 |
| | SQUARE FEET (0.53 M2). |
| | |
| | EXCEPTION: THE MINIMUM NET CLEAR OPENING FOR EMERGENCY |
| | ESCAPE AND RESCUE GRADE-FLOOR OPENINGS SHALL BE 5 |
| | SQUARE FEET (0.46 M2). |
| | |
| | 1026.2.1 MINIMUM DIMENSIONS. THE MINIMUM NET CLEAR |
| | OPENING HEIGHT DIMENSION SHALL BE 24 INCHES (610 MM). |
| | THE MINIMUM NET CLEAR OPENING WIDTH DIMENSION SHALL BE |
| | 20 INCHES (508 MM). THE NET CLEAR OPENING DIMENSIONS |
| | SHALL BE THE RESULT OF NORMAL OPERATION OF THE OPENING. |
| | |
| | 1026.3 MAXIMUM HEIGHT FROM FLOOR. EMERGENCY ESCAPE AND |
| | RESCUE OPENINGS SHALL HAVE THE BOTTOM OF THE CLEAR |
| | OPENING NOT GREATER THAN 44 INCHES (1118 MM) MEASURED |
| | FROM THE FLOOR. |
| | |
| | 6)EXT BLD CODE 906.1 GENERAL. ACCESSIBILITY IN PORTIONS |
| | OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| | CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE |
| | FLORIDA BUILDING CODE, BUILDING . |
| | EXT BLD CODE912.8 ACCESSIBILITY. EXISTING BUILDINGS OR |
| | PORTIONS THEREOF THAT UNDERGO A CHANGE OF GROUP OR |
| | OCCUPANCY CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |