| Plan Review Notes For Permit 10060659 |
| Permit Number |
10060659 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-23 20:38:00 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PLEASE EXPLAIN, PLAN SHOWS INSULATION ON INTERIOR | | | WALLS WITH VAPOR BARRIER. VAPOR BARRIER IS NOT | | | TYPICALLY USED IN INTERIOR WALLS DUE TO MOISTURE | | | ISSUES. PLEASE PROVIDE DOCUMENTATION FROM THE | | | MANUFACTURER WHICH SHOWS THAT THIS IS ACCEPTABLE. | | | | | | 2. INSULATION IS TYPICALLY INSTALLED IN ADJACENT WALLS | | | (WALLS BETWEEN CONDITIONED AND UNCONDITIONED SPACE), | | | EXTERIOR WALLS, AND CEILINGS. PLAN SHOWS INSULATION TO | | | BE INSTALLED ON INTERIOR WALLS. PLEASE EXPLAIN. | | | | | | 3. HOW WILL THE BATT INSULATION BE INSTALLED? OUR | | | RECORDS DO NOT SHOW EVIDENCE OF A PERMIT TO REMOVE OR | | | INSTALL DRYWALL. THIS MAY BE ADDED TO THE SCOPE OF WORK | | | FOR THIS PERMIT (AND ALSO REVISE VALUE). | | | |
|