| Plan Review Notes For Permit 10060646 |
| Permit Number |
10060646 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-22 14:47:46 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT | | | SIZING CALCULATIONS USING A CODE APPROVED METHOD AS | | | REQUIRED BY FBC R M1401.3. | | | | | | 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE | | | STRUCTURE. | | | | | | 3) SUBMIT 2 SETS OF MECHANICAL PLANS. SPECIFY THE | | | SUPPLY AND RETURN DUCT SIZES, GRILL SIZES, LOCATIONS, | | | CFMS. SPECIFY THE LOCATIONS OF THE AHU AND CONDENSER | | | WITH REQUIRED DISCONNECTS AND SERVICE OUTLETS. SHOW | | | COMPLIANCE WITH FBC R M1602.4 FOR BALANCED RETURN AIR. | | | SPECIFY THE HVAC EQUIPMENT THAT WILL BE INSTALLED ON | | | THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|