| Plan Review Notes For Permit 10060646 |
| Permit Number |
10060646 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-22 16:52:47 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO SETS OF STRUCTURAL PLANS FOR THE FRONT | | | PORCH. SPECIFY ALL STRAPS AND CONNECTORS. SHOW THAT | | | CONSTRUCTION COMPLIES WITH WINDLOADS AND THAT A | | | CONTINUOUS LOAD PATH FROM THE ROOF TO THE FOUNDATION IS | | | PROVIDED. SPECIFY ROOF PITCH, ROOF FRAMING, ROOF | | | SHEATHING, SHEATHING FASTENERS & SPACING, ROOF | | | COVERING, HEADER AND COLUMN SIZES AND ATTACHMENTS. SHOW | | | ALL DIMENSIONS ON THE PLANS. SPECIFY THE DESIGN | | | CRITERIA ON THE PLANS. | | | | | | 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR ROOF | | | COVERING, HURRICANE CONNECTORS AND STRAPS, WINDOWS, | | | STRUCTURAL MULLIONS AND IMPACT PROTECTION DEVICES AS | | | REQUIRED BY DCA RULE 9B-72. | | | | | | 3) SUBMIT 2 COPIES OF A FLOOR PLAN SHOWING THE NEW | | | WINDOW TYPES, SIZES AND LOCATIONS. INDICATE WHICH | | | WINDOWS WILL BE MULLED TOGETHER. IDENTIFY THE ROOMS ON | | | THE FLOOR PLAN, SUCH AS BEDROOM, BATHROOM, ETC. | | | | | | 4) IF STORM PANELS ARE TO BE INSTALLED 2 COPIES OF A | | | KEY PLAN AND AN INSTALLATION SCHEDULE WILL BE REQUIRED. | | | THE WINDLOAD PRESSURES, ANCHOR TYPE AND SPACING, MOUNT | | | TYPE, EDGE DISTANCE, SPAN, GLASS SEPARATION WILL | | | REQUIRED. | | | | | | 5) TWO COPIES OF A SURVEY OR SITE PLAN INDICATING THE | | | DISTANCE TO PROPERTY LINES OF THE PORCH ARE REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|