2010-07-12 13:33:392007 FBC W/2009 REVISIONS
 POOL
  
 DENIED BY PLUMBING
  
 1) THE POOL PUMP IS SPECIFIED AS A 1.5 HP IN THE FLOW
 RATE CALCULATIONS ON THE PLANS AND AS A 1 HP PUMP AT
 THE OTHER LOCATIONS ON SHEET 1. PLEASE CORRECT. THE
 ALLOWABLE FLOW RATES WILL BE EXCEEDED IF THE 1.5 HP
 PUMP IS INSTALLED.
  
 2) SUBMIT TWO COPIES OF THE SPECIFICATIONS AND PRODUCT
 DATA SHEETS WHICH INDICATE THE LOSS IN TDH FOR THE GAS
 POOL HEATER AND CARTRIDGE FILTER THAT WILL BE
 INSTALLED.
  