| Plan Review Notes For Permit 10060578 |
| Permit Number |
10060578 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-08-09 16:13:51 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE INSTALLATION SCHEDULE FOR THE STORM PANELS | | | INDICATE THAT THE H-HEADER AT THE TOP IS TO BE ANCHORED | | | TO BLOCK. THE PRODUCT APPROVAL REQUIRES POURED CONCRETE | | | FOR THIS INSTALLATION. SEE SHEET 2 OF 9 AND THE TABLE | | | ON SHEET 5 OF 9. PLEASE CORRECT. | | | | | | 2) PROVIDE A DETAIL OF THE COLUMN CAP AT THE TOP OF THE | | | NEW ALUMINUM COLUMN ON THE PLAN. | | | | | | 3) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR | | | THE RAFTERS AT THE LAUNDRY ROOM AND PORCH. | | | | | | 4) SPECIFY THE EXTERIOR WALL COVERING THAT WILL BE USED | | | ON THE LAUNDRY ROOM ON THE PLANS. SHOW COMPLIANCE WITH | | | FBC R319 FOR CLEARANCE TO GROUND AND FBC R704.1 FOR | | | CLEARANCE FOR TERMITE INSPECTION. | | | | | | 5) THE STRUCTURE IS LOCATED IN A 140 MPH WIND SPEED AND | | | EXPOSURE CATEGORY C. SPECIFY THE WIND SPEED AND | | | EXPOSURE CATEGORY ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|