2010-08-23 17:02:06OK PER JOHN DICKINSON CONTRACTOR PLAN REVIEWER LICENSE
 PX 3182
2010-08-23 17:01:17NEW SUBMITED LOAD CALCUATIONS AND PANEL SCHEDULE DO NOT
 MATCH,LOADCALCUATION SHOWS 87.5 AMPS ON 100 AMP FEEDER
 AND PANEL, WITHOUT WATER HEATER, WATER HEATER HEATER
 SHOWN ON PANEL SCHEDULE,SHOW FACTORY INSTALLED FEEDER
 SIZE IN 11/4 CONDUIT BETWEEN EXISTING 150AMP PANEL AND
 NEW TRANSFER SWITCH PANEL COMBO