| 2010-08-23 17:02:06 | OK PER JOHN DICKINSON CONTRACTOR PLAN REVIEWER LICENSE | | | PX 3182 | | 2010-08-23 17:01:17 | NEW SUBMITED LOAD CALCUATIONS AND PANEL SCHEDULE DO NOT | | | MATCH,LOADCALCUATION SHOWS 87.5 AMPS ON 100 AMP FEEDER | | | AND PANEL, WITHOUT WATER HEATER, WATER HEATER HEATER | | | SHOWN ON PANEL SCHEDULE,SHOW FACTORY INSTALLED FEEDER | | | SIZE IN 11/4 CONDUIT BETWEEN EXISTING 150AMP PANEL AND | | | NEW TRANSFER SWITCH PANEL COMBO |
|