Plan Review Notes
Plan Review Notes For Permit 10060532
Permit Number 10060532
Review Stop Z
Sequence Number 1
Notes
Date Text
2010-07-07 10:58:41FAILED
  
 1) PROVIDE TWO COPIES OF A SURVEY, LESS THAN ONE YEAR
 OLD, WHICH SHOWS THE EXISTING STRUCTURES AND THE
 SETBACKS OF THE STRUCTURES TO THE PROPERTY LINES.
  
 2) PROVIDE THE GENERATOR AND PAD LOCATION ON A SITE
 PLAN, OR MARKED UP COPY OF THE SURVEY, WHICH SHOWS THE
 PROPOSED GENERATOR LOCATION, INCLUDING SETBACKS FROM
 THE PROPERTY LINES AND THE BUILDING. THE BUILDING
 SETBACKS WILL DETERMINE THE GENERATOR SETBACK.
 GENERATOR MAY NOT ENCROACH MORE THAN FOUR (4) FEET INTO
 A REQUIRED SETBACK.
  
 3) PROVIDE THE EXACT DIMENSIONS OF THE GENERATOR AND
 THE PAD.
  
 4) IS ANY LANDSCAPE (TREES OR SHRUBS) BEING AFFECTED BY
 THE GENERATOR INSTALLATION? SHRUBS SHALL BE RELOCATED
 ON-SITE. IF TREES ARE BEING IMPACTED, THEN A TREE
 ALTERATION PERMIT IS REQUIRED FROM THE PLANNING AND
 ZONING DEPARTMENT PRIOR TO THE TREE IMPACT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.