Plan Review Notes
Plan Review Notes For Permit 10060532
Permit Number 10060532
Review Stop E
Sequence Number 1
Notes
Date Text
2010-06-30 08:29:25THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
  
 1} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE
 GENERATOR AND TRANSFER SWITCH.
  
 2} PROVIDE A CALCULATION FOR THE LOAD BEING SERVED BY
 THE GENERATOR.
  
 3} PROVIDE FEEDER SIZES FROM THE GENERATOR TO THE ATS.
  
 4} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR AND MATERIAL FOR THE GENERATOR,
 EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.), AND PAD PER
 108.3 FBC AS AMENDED.
 INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING,
 AND GET A RECEIPT FROM THE PERMIT CLERK.
  