| 2010-06-30 08:29:25 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | 1} PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING | | | RECOMMENDED SETBACKS AND ELECTRICAL SPEC'S FOR THE | | | GENERATOR AND TRANSFER SWITCH. | | | | | | 2} PROVIDE A CALCULATION FOR THE LOAD BEING SERVED BY | | | THE GENERATOR. | | | | | | 3} PROVIDE FEEDER SIZES FROM THE GENERATOR TO THE ATS. | | | | | | 4} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL FOR THE GENERATOR, | | | EQUIPMENT(TRANSFER SWITCHES, PANELS ETC.), AND PAD PER | | | 108.3 FBC AS AMENDED. | | | INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING, | | | AND GET A RECEIPT FROM THE PERMIT CLERK. | | | |
|