| Plan Review Notes For Permit 10060422 |
| Permit Number |
10060422 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-11-03 15:54:27 | RESIDENTIAL (R3) MECHANICAL REVIEW SECOND CHECKLIST. | | | (REPEAT COMMENTS. NOT ADDRESSED). | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS. NONE | | | SUBMITTED. | | | | | | 2- PROVIDE MANUAL J CALCULATIONS FOR EQUIPMENT SIZING. | | | NONE SUBMITTED. | | | | | | 3- PROVIDE MECHANICAL VENTILATION IN BATHROOM AS | | | REQUIRED BY SEC. M1507 OF 2007 FLORIDA RESIDENTIAL | | | CODE. OR PROVIDE COMPLIANCE WITH THE VENTILATION | | | REQUIREMENTS OF SEC. R303.3 | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|