| 2010-11-03 11:18:41 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND |
| | CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- A) PROPERTY IS LOCATED ON FLOOD ZONE A5. EXISTING |
| | HOUSE AND NEW ADDITION NEED TO HAVE A MINIMUM FINISHED |
| | FLOOR ELEVATION OF 7'-6" AS REQUIRED BY CITY ORDINANCE |
| | SEC. 94-546 (A)(B). SURVEY AND PROPOSED PLANS NEED TO |
| | SHOW THE NEW REQUIRED FINISHED FLOOR ELEVATION. |
| | |
| | RESPONSE TO SUBMITTAL: |
| | * FINISH FLOOR ELEVATION SHOWN ON PLANS DON'T MATCH ONE |
| | SHOWN ON NEW SURVEY. ** FLOOR PLANS DON'T SHOW THE |
| | FINISH FLOOR ELEVATION OF THE NEW ADDITION. |
| | |
| | B) CERTIFICATE ELEVATION WILL BE REQUIRED. (THIS WILL |
| | BE REQUIRED LATER ON DURING CONSTRUCTION TO VERIFY |
| | FINISH FLOOR ELEVATION). |
| | |
| | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 3- ENGINEER OF RECORD TO REVISE THE DESIGN PARAMETERS |
| | ON SHEET #1: |
| | A) CURRENT BUILDING CODE IS THE FBC 2007 WITH 2009 |
| | REVISIONS, NOT FBC 2009 WITH 2009 REVISIONS. REVISE |
| | NOTES UNDER THE ROOF PLAN NOTES ALSO. |
| | |
| | B) ENGINEER NEEDS TO INCREASE THE ROOF SHEATHING UPLIFT |
| | AND ROOF-TO-WALL UPLIFT LOADS BY 20% AS REQUIRED BY |
| | SEC. R301.2.1.4.3(2). SHOW COMPLIANCE WITH THIS |
| | SECTION. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | C) ONLY THE ROOF TOTAL DEAD LOAD WAS PROVIDED. SPECIFY |
| | ALL DEAD AND LIVE LOADS INCLUDING THE ATTIC LIVE LOAD |
| | AS REQUIRED BY TABLE R301.5 (REPEAT COMMENT. NOT |
| | ADDRESSED). |
| | |
| | 4- SHEET #2: PROVIDE DIMENSIONS FOR NEW SHOWER AND |
| | TOILET ROOM TO VERIFY COMPLIANCE WITH THE CLEARANCES |
| | REQUIRED BY FIGURE R307.1. NOTE: CHECK THE 21 IN. |
| | CLEARANCE REQUIRED IN FRONT OF THE TOILET. (REPEAT |
| | COMMENT. FLOOR PLAN DOESN'T PROVIDE THE ROOM |
| | DIMENSIONS. IT ONLY SHOWS 2' FROM THE WATER CLOSET TO |
| | THE CENTER OF THE DOOR. ALL WATER CLOSETS ARE NO THE |
| | SAME. NEED TO PROVIDE ACTUAL ROOM DIMENSIONS ON PLANS |
| | FOR BOTH WATER CLOSET AND SHOWER ENCLOSURES). |
| | |
| | 5- SHEET #4: |
| | A) REVISE GABLE END DETAIL TO COMPLY WITH SEC. R609.4 |
| | AND SEC. R601.2. NEED TO PROVIDE A CONTINUOUS LOAD PATH |
| | WALL AND ROOF. PROVIDE COMPLETE SPECIFICATIONS FOR ALL |
| | CONNECTORS. EG: SIZE AND SPACING. ALSO, COORDINATE |
| | INFORMATION WITH REQUIREMENTS OF ITEM 3(B) ABOVE. |
| | (REPEAT COMMENT). THERE IS NO INFORMATION OF HOW IS THE |
| | GABLE END ROOF TRUSS ATTACHED TO THE BOND BEAM TO |
| | PROVIDE CONTINUOUS LOAD PATH TO THE WALL. ALSO, |
| | COORDINATE WITH ITEM #3(B) ABOVE. |
| | |
| | B) PROVIDE CALCULATIONS SHOWING COMPLIANCE WITH THE |
| | SIZE AND SPACING OF ATTIC VENTILATION SHOWN ON WALL |
| | SECTION TO COMPLY WITH THE VENTILATION REQUIREMENTS OF |
| | SEC. R806. |
| | (REPEAT COMMENT). CALCULATIONS SUBMITTED ARE INCORRECT. |
| | NEED TO PROVIDE CALCULATIONS FOR ENTIRE "ATTIC" |
| | VENTILATION, NOT JUST FOR THE "SOFFIT" VENTILATION. |
| | REVISE AS REQUIRED. |
| | |
| | 6- SHEET #5: |
| | A) ENGINEER OF RECORD TO REVISE CONNECTORS SPECIFIED TO |
| | COMPLY WITH THE REQUIREMENTS SHOWN ON ITEM 3(B) ABOVE. |
| | (REPEAT COMMENT. NOT ADDRESSED). ENGINEER TO SPECIFY ON |
| | PLANS IF THE ROOF SHEATHING UPLIFT AND ROOF TO WALL |
| | UPLIFT LOADS WERE INCREASED BY 20% AS REQUIRED BY SEC. |
| | R301.2.1.4.3(2). |
| | |
| | B) AND, CLARIFY CONNECTOR SHOWN ON TRUSS LAYOUT FOR |
| | GABLE END TRUSSES. COORDINATE WITH ITEM #3(B) AND #5(A) |
| | ABOVE. |
| | |
| | C) TRUSS ENGINEER SHOWN ON THE TRUSS LAYOUT TO PROVIDE |
| | ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 |
| | FLORIDA STATUTE. |
| | ***NOTE: TYPICALLLY THE TRUSS ENGINEER PROVIDES TRUSS |
| | LAYOUT AND INDIVIDUAL TRUSS ENGINEERING ON SEPARATE |
| | PACKAGE. |
| | |
| | 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | ***NOTE: THIS MAY DE DONE LATER ON BEFORE PERMIT IS |
| | READY TO BE ISSUED. |
| | |
| | 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 9- ENGINEER OF RECORD TO PROVIDE HIS LICENSE NUMBER AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. (REPEAT |
| | COMMENT. DRAWINGS SUBMITTED ARE NOW MISSING THE |
| | ENGINEER OF RECORD INFORMATION (NAME, LICENSE #, |
| | ADDRESS, ETC) ON EACH DRAWING. |
| | |
| | 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) HARDIPLANK SOFFIT AS SPECIFIED ON PLANS. NOTE: CHECK |
| | FRAMING MEMBERS SPACING REQUIRED ON THE PRODUCT |
| | APPROVAL AND FRAMING MEMBER SHOWN ON PLANS TO MAKE SURE |
| | INSTALLATION WILL BE DONE ACCORDING TO THE PRODUCT |
| | APPROVAL REQUIREMENTS. (REPEAT COMMENT, NOT ADDRESSED) |
| | ENGINEER TO CHECK SHEET 3/3 OF NOA 07-0418.04 SUBMITTED |
| | AND REVISE FRAMING MEMBERS SPACING AS REQUIRED. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | C) MASTER BATH EXTERIOR DOOR AS SHOWN ON PLANS. (REPEAT |
| | COMMENT. NOT ADDRESSED). |
| | |
| | D) CLARIFY WHICH ROOFING TYPE IS GOING TO BE INSTALLED. |
| | THREE DIFFERENT PRODUCT APPROVALS WHERE SUBMITTED: ROOF |
| | TILE, SHINGLES AND METAL ROOFING PANELS. WHICH ONE IS |
| | GOING TO BE INSTALLED? |
| | |
| | 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS |
| | (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY |
| | SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | ***SUBMITTAL RESPONSE: ENGINEER TO PROVIDE ALL HIS |
| | INFORMATION (NAME, LICENSE NUMBER, ADDRESS, ETC) ON |
| | LETTER SUBMITTED. AND, MAKE SURE MISSING PRODUCT |
| | APPROVALS ARE INCLUDED. |
| | |
| | 12- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED |
| | TO COMPLY WITH SEC. R807. |
| | ***SUBMITTAL RESPONSE: REVISED FLOOR PLAN ON SHEET #2 |
| | SHOWS NEW 22" X 56" PULL DOWN STAIRCASE. NEED TO |
| | PROVIDE OPENING FRAMING DETAILS. ACCORDING TO ROOF |
| | PLANS NEED TO CUT THE TRUSSES TO ALLOW FOR THE NEW |
| | OPENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 13- OWES $725.38. INCLUDES PERMIT FEE BALANCE, UPDATED |
| | VALUATION AND RADON FEES. |
| | ***THIS MAY BE PAID AT TIME OF PERMIT PICK UP. |
| | |
| | 14- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER |
| | 11 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT. |
| | NOT ADDRESSED). |
| | |
| | 15- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED). |
| | A) TRUSS PACKAGE NEED TO BE RE-DESIGNED TO COMPLY WITH |
| | THE 20% UPLIFT INCREASE AS REQUIRED BY SEC. |
| | R301.2.1.4.3(2). SEE ITEM #3(C) ABOVE. |
| | B) NEED ORIGINAL TRUSS ENGINEER SEAL AND SIGNATURE ON |
| | BOTH COPIES SUBMITTED. |
| | C) REVISE TRUSS DRAWINGS TO SHOW THE ATTIC LIVE LOAD AS |
| | REQUIRED BY TABLE R301.5. |
| | D) TRUSS ENGINEER TO PROVIDE ALL THE INFORMATION ON THE |
| | COVER SHEET AS REQUIRED BY SEC. 61G15-31.003 OF FLORIDA |
| | ADMINISTRATIVE CODE IF SIGNING AND SEALING ONLY THE |
| | COVER PAGE INSTEAD OF SIGNING AND SEALING EACH |
| | INDIVIDUAL SHEET. IN ADDITION EACH INDIVIDUAL SHEET |
| | NEED TO HAVE THE TRUSS ENGINEER INFORMATION AS |
| | REQUESTED BY THIS SECTION ALSO. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |