Plan Review Notes
Plan Review Notes For Permit 10060422
Permit Number 10060422
Review Stop B
Sequence Number 2
Notes
Date Text
2010-11-03 11:18:41RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- A) PROPERTY IS LOCATED ON FLOOD ZONE A5. EXISTING
 HOUSE AND NEW ADDITION NEED TO HAVE A MINIMUM FINISHED
 FLOOR ELEVATION OF 7'-6" AS REQUIRED BY CITY ORDINANCE
 SEC. 94-546 (A)(B). SURVEY AND PROPOSED PLANS NEED TO
 SHOW THE NEW REQUIRED FINISHED FLOOR ELEVATION.
  
 RESPONSE TO SUBMITTAL:
 * FINISH FLOOR ELEVATION SHOWN ON PLANS DON'T MATCH ONE
 SHOWN ON NEW SURVEY. ** FLOOR PLANS DON'T SHOW THE
 FINISH FLOOR ELEVATION OF THE NEW ADDITION.
  
 B) CERTIFICATE ELEVATION WILL BE REQUIRED. (THIS WILL
 BE REQUIRED LATER ON DURING CONSTRUCTION TO VERIFY
 FINISH FLOOR ELEVATION).
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 3- ENGINEER OF RECORD TO REVISE THE DESIGN PARAMETERS
 ON SHEET #1:
 A) CURRENT BUILDING CODE IS THE FBC 2007 WITH 2009
 REVISIONS, NOT FBC 2009 WITH 2009 REVISIONS. REVISE
 NOTES UNDER THE ROOF PLAN NOTES ALSO.
  
 B) ENGINEER NEEDS TO INCREASE THE ROOF SHEATHING UPLIFT
 AND ROOF-TO-WALL UPLIFT LOADS BY 20% AS REQUIRED BY
 SEC. R301.2.1.4.3(2). SHOW COMPLIANCE WITH THIS
 SECTION. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) ONLY THE ROOF TOTAL DEAD LOAD WAS PROVIDED. SPECIFY
 ALL DEAD AND LIVE LOADS INCLUDING THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE R301.5 (REPEAT COMMENT. NOT
 ADDRESSED).
  
 4- SHEET #2: PROVIDE DIMENSIONS FOR NEW SHOWER AND
 TOILET ROOM TO VERIFY COMPLIANCE WITH THE CLEARANCES
 REQUIRED BY FIGURE R307.1. NOTE: CHECK THE 21 IN.
 CLEARANCE REQUIRED IN FRONT OF THE TOILET. (REPEAT
 COMMENT. FLOOR PLAN DOESN'T PROVIDE THE ROOM
 DIMENSIONS. IT ONLY SHOWS 2' FROM THE WATER CLOSET TO
 THE CENTER OF THE DOOR. ALL WATER CLOSETS ARE NO THE
 SAME. NEED TO PROVIDE ACTUAL ROOM DIMENSIONS ON PLANS
 FOR BOTH WATER CLOSET AND SHOWER ENCLOSURES).
  
 5- SHEET #4:
 A) REVISE GABLE END DETAIL TO COMPLY WITH SEC. R609.4
 AND SEC. R601.2. NEED TO PROVIDE A CONTINUOUS LOAD PATH
 WALL AND ROOF. PROVIDE COMPLETE SPECIFICATIONS FOR ALL
 CONNECTORS. EG: SIZE AND SPACING. ALSO, COORDINATE
 INFORMATION WITH REQUIREMENTS OF ITEM 3(B) ABOVE.
 (REPEAT COMMENT). THERE IS NO INFORMATION OF HOW IS THE
 GABLE END ROOF TRUSS ATTACHED TO THE BOND BEAM TO
 PROVIDE CONTINUOUS LOAD PATH TO THE WALL. ALSO,
 COORDINATE WITH ITEM #3(B) ABOVE.
  
 B) PROVIDE CALCULATIONS SHOWING COMPLIANCE WITH THE
 SIZE AND SPACING OF ATTIC VENTILATION SHOWN ON WALL
 SECTION TO COMPLY WITH THE VENTILATION REQUIREMENTS OF
 SEC. R806.
 (REPEAT COMMENT). CALCULATIONS SUBMITTED ARE INCORRECT.
 NEED TO PROVIDE CALCULATIONS FOR ENTIRE "ATTIC"
 VENTILATION, NOT JUST FOR THE "SOFFIT" VENTILATION.
 REVISE AS REQUIRED.
  
 6- SHEET #5:
 A) ENGINEER OF RECORD TO REVISE CONNECTORS SPECIFIED TO
 COMPLY WITH THE REQUIREMENTS SHOWN ON ITEM 3(B) ABOVE.
 (REPEAT COMMENT. NOT ADDRESSED). ENGINEER TO SPECIFY ON
 PLANS IF THE ROOF SHEATHING UPLIFT AND ROOF TO WALL
 UPLIFT LOADS WERE INCREASED BY 20% AS REQUIRED BY SEC.
 R301.2.1.4.3(2).
  
 B) AND, CLARIFY CONNECTOR SHOWN ON TRUSS LAYOUT FOR
 GABLE END TRUSSES. COORDINATE WITH ITEM #3(B) AND #5(A)
 ABOVE.
  
 C) TRUSS ENGINEER SHOWN ON THE TRUSS LAYOUT TO PROVIDE
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
 ***NOTE: TYPICALLLY THE TRUSS ENGINEER PROVIDES TRUSS
 LAYOUT AND INDIVIDUAL TRUSS ENGINEERING ON SEPARATE
 PACKAGE.
  
 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 ***NOTE: THIS MAY DE DONE LATER ON BEFORE PERMIT IS
 READY TO BE ISSUED.
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 9- ENGINEER OF RECORD TO PROVIDE HIS LICENSE NUMBER AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE. (REPEAT
 COMMENT. DRAWINGS SUBMITTED ARE NOW MISSING THE
 ENGINEER OF RECORD INFORMATION (NAME, LICENSE #,
 ADDRESS, ETC) ON EACH DRAWING.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) HARDIPLANK SOFFIT AS SPECIFIED ON PLANS. NOTE: CHECK
 FRAMING MEMBERS SPACING REQUIRED ON THE PRODUCT
 APPROVAL AND FRAMING MEMBER SHOWN ON PLANS TO MAKE SURE
 INSTALLATION WILL BE DONE ACCORDING TO THE PRODUCT
 APPROVAL REQUIREMENTS. (REPEAT COMMENT, NOT ADDRESSED)
 ENGINEER TO CHECK SHEET 3/3 OF NOA 07-0418.04 SUBMITTED
 AND REVISE FRAMING MEMBERS SPACING AS REQUIRED.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. (REPEAT COMMENT. NOT ADDRESSED).
  
 C) MASTER BATH EXTERIOR DOOR AS SHOWN ON PLANS. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 D) CLARIFY WHICH ROOFING TYPE IS GOING TO BE INSTALLED.
 THREE DIFFERENT PRODUCT APPROVALS WHERE SUBMITTED: ROOF
 TILE, SHINGLES AND METAL ROOFING PANELS. WHICH ONE IS
 GOING TO BE INSTALLED?
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 106.3.3 CITY AMENDMENTS TO FBC.
 ***SUBMITTAL RESPONSE: ENGINEER TO PROVIDE ALL HIS
 INFORMATION (NAME, LICENSE NUMBER, ADDRESS, ETC) ON
 LETTER SUBMITTED. AND, MAKE SURE MISSING PRODUCT
 APPROVALS ARE INCLUDED.
  
 12- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 TO COMPLY WITH SEC. R807.
 ***SUBMITTAL RESPONSE: REVISED FLOOR PLAN ON SHEET #2
 SHOWS NEW 22" X 56" PULL DOWN STAIRCASE. NEED TO
 PROVIDE OPENING FRAMING DETAILS. ACCORDING TO ROOF
 PLANS NEED TO CUT THE TRUSSES TO ALLOW FOR THE NEW
 OPENING. SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 13- OWES $725.38. INCLUDES PERMIT FEE BALANCE, UPDATED
 VALUATION AND RADON FEES.
 ***THIS MAY BE PAID AT TIME OF PERMIT PICK UP.
  
 14- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 11 OF 2007 FLORIDA RESIDENTIAL CODE. (REPEAT COMMENT.
 NOT ADDRESSED).
  
 15- TRUSS PACKAGE: (REPEAT COMMENT. NOT ADDRESSED).
 A) TRUSS PACKAGE NEED TO BE RE-DESIGNED TO COMPLY WITH
 THE 20% UPLIFT INCREASE AS REQUIRED BY SEC.
 R301.2.1.4.3(2). SEE ITEM #3(C) ABOVE.
 B) NEED ORIGINAL TRUSS ENGINEER SEAL AND SIGNATURE ON
 BOTH COPIES SUBMITTED.
 C) REVISE TRUSS DRAWINGS TO SHOW THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5.
 D) TRUSS ENGINEER TO PROVIDE ALL THE INFORMATION ON THE
 COVER SHEET AS REQUIRED BY SEC. 61G15-31.003 OF FLORIDA
 ADMINISTRATIVE CODE IF SIGNING AND SEALING ONLY THE
 COVER PAGE INSTEAD OF SIGNING AND SEALING EACH
 INDIVIDUAL SHEET. IN ADDITION EACH INDIVIDUAL SHEET
 NEED TO HAVE THE TRUSS ENGINEER INFORMATION AS
 REQUESTED BY THIS SECTION ALSO.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  