Plan Review Notes
Plan Review Notes For Permit 10060422
Permit Number 10060422
Review Stop B
Sequence Number 1
Notes
Date Text
2010-07-07 13:48:22RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- A) PROPERTY IS LOCATED ON FLOOD ZONE A5. EXISTING
 HOUSE AND NEW ADDITION NEED TO HAVE A MINIMUM FINISHED
 FLOOR ELEVATION OF 7'-6" AS REQUIRED BY CITY ORDINANCE
 SEC. 94-546 (A)(B). SURVEY AND PROPOSED PLANS NEED TO
 SHOW THE NEW REQUIRED FINISHED FLOOR ELEVATION.
 B) CERTIFICATE ELEVATION WILL BE REQUIRED.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 3- ENGINEER OF RECORD TO REVISE THE DESIGN PARAMETERS
 ON SHEET #1:
 A) ACCORDING TO 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED ON EXPOSURE "C" NOT EXPOSURE "B".
 B) REVISE THE CALCULATED DOORS AND WINDOWS DESIGN
 PRESSURES.
 C) ENGINEER NEEDS TO INCREASE THE ROOF SHEATHING UPLIFT
 AND ROOF-TO-WALL UPLIFT LOADS BY 20% AS REQUIRED BY
 SEC. R301.2.1.4.3(2). SHOW COMPLIANCE WITH THIS
 SECTION.
 D) ONLY THE ROOF TOTAL DEAD LOAD WAS PROVIDED. SPECIFY
 ALL DEAD AND LIVE LOADS INCLUDING THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE R301.5
 E) DIMENSIONS SHOWN ON PLOT PLAN DON'T MATCH DIMENSIONS
 SHOWN ON SURVEY AND ON NEW FLOOR PLAN ON SHEET #2.
 REVISE AS REQUIRED TO MATCH.
  
 4- SHEET #2: PROVIDE DIMENSIONS FOR NEW SHOWER AND
 TOILET ROOM TO VERIFY COMPLIANCE WITH THE CLEARANCES
 REQUIRED BY FIGURE R307.1. NOTE: CHECK THE 21 IN.
 CLEARANCE REQUIRED IN FRONT OF THE TOILET.
  
 4- SHEET #3:
 A)REVISE WINDOW BUCKS AND DOORS BUCKS SPECIFICATIONS.
 THE PROPOSED CONSTRUCTION IS CONCRETE BLOCK NOT WOOD
 FRAMING.
 B) BEVELED BUCKS ARE NOT ALLOWED. BUCK SIZE NEED TO
 PROVIDE FULL SUPPORT TO THE WINDOW AND DOOR FRAME.
 REVISE AS REQUIRED SEE SEC. R613.6.
  
 5- SHEET #4:
 A) REVISE GABLE END DETAIL TO COMPLY WITH SEC. R609.4
 AND SEC. R601.2. NEED TO PROVIDE A CONTINUOUS LOAD PATH
 WALL AND ROOF. PROVIDE COMPLETE SPECIFICATIONS FOR ALL
 CONNECTORS. EG: SIZE AND SPACING. ALSO, COORDINATE
 INFORMATION WITH REQUIREMENTS OF ITEM 3(C) ABOVE.
 B) REVISE STUCCO THICKNESS ON GABLE END. 7/8" MIN.
 STUCCO THICKNESS IS REQUIRED BY TABLE R702.1(1).
 C) SPECIFY 2 LAYERS OF APPROVED WATER-RESISTANT BARRIER
 ON GABLE END AS REQUIRED BY SEC. R703.6.3.
 D) SPECIFY ROOF SHEATHING NAILING SIZE AND SPACING AS
 REQUIRED BY SEC. R803.2.3.1. NEED TO USE MIN. 8D RING
 SHANK NAILS AND SPACING TO BE 4"O.C. IN ROOF ZONE 3.
 E) PROVIDE CALCULATIONS SHOWING COMPLIANCE WITH THE
 SIZE AND SPACING OF ATTIC VENTILATION SHOWN ON WALL
 SECTION TO COMPLY WITH THE VENTILATION REQUIREMENTS OF
 SEC. R806.
  
 6- SHEET #5:
 A) REVISE CONNECTORS SPECIFIED TO COMPLY WITH THE
 REQUIREMENTS SHOWN ON ITEM 3(C) ABOVE.
 AND CLARIFY CONNECTOR SHOWN ON TRUSS LAYOUT FOR TRUSSES
 T-1G AND T-2G.
 B) REVISE THE BOTTOM CHORD LIVE LOAD TO COMPLY WITH
 TABLE R301.5. NEED TO SPECIFY THE LIVE LOAD IN THE
 ATTIC.
 C) TRUSS ENGINEER SHOWN ON THE TRUSS LAYOUT TO PROVIDE
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FLORIDA STATUTE.
  
 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 8- PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4.
  
 9- ENGINEER OF RECORD TO PROVIDE HIS LICENSE NUMBER AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 10- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) GLASS BLOCK AS SPECIFIED ON PLANS.
 B) HARDIPLANK SOFFIT AS SPECIFIED ON PLANS. NOTE: CHECK
 FRAMING MEMBERS SPACING REQUIRED ON THE PRODUCT
 APPROVAL AND FRAMING MEMBER SHOWN ON PLANS TO MAKE SURE
 INSTALLATION WILL BE DONE ACCORDING TO THE PRODUCT
 APPROVAL REQUIREMENTS.
 C) ALL STRUCTURAL CONNECTORS SPECIFIED ON PLANS.
 D) MASTER BATH EXTERIOR DOOR.
  
 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS
 (INCLUDING THE ONES ALREADY SUBMITTED) AS REQUIRED BY
 SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 12- PLANS NEED TO SPECIFY CARBON MONOXIDE ALARM AS
 REQUIRED BY SEC. R313.4.
  
 13- SPECIFY ATTIC ACCESS SIZE AND LOCATION AS REQUIRED
 TO COMPLY WITH SEC. R807.
  
 14- OWES $725.38. INCLUDES PERMIT FEE BALANCE, UPDATED
 VALUATION AND RADON FEES.
  
 15- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY CHAPTER
 11 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 16- ENGINEER OF RECORD TO SPECIFY ALTERATION TYPE AS
 REQUIRED BY SEC. 401.4 OF 2007 FBC-EXISTING BUILDING
 CODE.
  
 17- SURVEY PROVIDED:
 A) NEW ADDITION DIMENSIONS DON'T MATCH DIMENSIONS SHOWN
 ON ENGINEER OF RECORD PLANS.
 B) SURVEYOR TO PROVIDE ORIGINAL SIGNATURE (NOT COPY) AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTE.
  
 18- TRUSS PACKAGE:
 A) TRUSS PACKAGE NEED TO BE RE-DESIGNED TO COMPLY WITH
 THE 20% UPLIFT INCREASE AS REQUIRED BY SEC.
 R301.2.1.4.3(2). SEE ITEM #3(C) ABOVE.
 B) NEED ORIGINAL TRUSS ENGINEER SEAL AND SIGNATURE ON
 BOTH COPIES SUBMITTED.
 C) REVISE TRUSS DRAWINGS TO SHOW THE ATTIC LIVE LOAD AS
 REQUIRED BY TABLE R301.5.
 D) TRUSS ENGINEER TO PROVIDE ALL THE INFORMATION ON THE
 COVER SHEET AS REQUIRED BY SEC. 61G15-31.003 OF FLORIDA
 ADMINISTRATIVE CODE IF SIGNING AND SEALING ONLY THE
 COVER PAGE INSTEAD OF SIGNING AND SEALING EACH
 INDIVIDUAL SHEET. IN ADDITION EACH INDIVIDUAL SHEET
 NEED TO HAVE THE TRUSS ENGINEER INFORMATION AS
 REQUESTED BY THIS SECTION ALSO.
  
 19- CLARIFY WHY THE OWNER LISTED ON THE PERMIT
 APPLICATION AND ON THE PROPERTY APPRAISAL WEBSITE IS
 DIFFERENT THAN THE OWNER LISTED ON THE DRAWINGS
 SUBMITTED. OWNER/BUILDER EXCEPTION APPLIES ONLY TO THE
 OWNER OF THE HOUSE. SEC. 489.103 FLORIDA STATUTE.
 REVISE PLANS ACCORDINGLY.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  