| Plan Review Notes For Permit 10060390 |
| Permit Number |
10060390 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-16 09:47:01 | RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PERMIT APPLICATION DESCRIBES REPAIR OF 800 S.F. OF | | | FLAT ROOF. CLARIFY IF REPAIR OR REPLACEMENT TO VERIFY | | | COMPLIANCE WITH SEC. 611 OF 2007 FBC-EXISTING BUILDING. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9B-72 FOR FLAT ROOF TO BE INSTALLED. | | | CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED. PROVIDE RAS 117 CALCULATIONS FOR NAIL | | | ENHANCING AT PERIMETER AND CORNER AREAS AS REQUIRED BY | | | GENERAL LIMITATION # 7 ON LAST PAGE OF NOA SUBMITTED. | | | PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS IF | | | GENERAL LIMITATION #7 REQUIRES IT. | | | ***NOTE: TAKE INTO CONSIDERATION THAT THIS BUILDING IS | | | LOCATED ON EXPOSURE "C" WHEN DOING THE RAS 117 | | | CALCULATIONS. | | | | | | 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTES. | | | | | | 4- SEPARATE PERMITS ARE REQUIRED WHEN REMOVING AND | | | RELOCATING ANY ROOF EQUIPMENT. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|