| Plan Review Notes For Permit 10060354 |
| Permit Number |
10060354 |
|
| Review Stop |
ENG |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-08-02 12:23:23 | PERMIT COMMENTS: | | | REVIEWER: DEAN S. LAUDERMILK, PROJECT COORDINATOR | | | CONTACT INFORMATION: DIRECT DIAL: 494-1083, FAX: | | | 494-1116, EMAIL: [email protected] | | | FAILED: | | | 1) THERE IS NO ROOF OVER THE DUMPSTER PAD. A SANITARY | | | SEWER CONNECTION CAN NOT BE MADE TO THE "FLOOR DRAINS" | | | UNLESS THE AREA IS COVERED BY A ROOF. TO ALLOW THIS | | | AREA TO DRAIN INTO THE SANITARY SEWER SYSTEM WOULD | | | ALLOW RAIN WATER ACCESS TO THE SANITARY SYSTEM, WHICH | | | IS NOT ALLOWED. THE ONLY WAY A DRAIN SYSTEM FOR THE | | | ENCLOSURE CAN BE ALLOWED IS TO HAVE IT ROOFED. | | | 2) PRIOR TO ALLOWING THE "FLOOR DRAINS" UNDER A ROOF WE | | | WOULD NEED TO SEE A SURVEY SHOWING THE GROUND OUTSIDE | | | OF THE ROOFED AREA DRAINS AWAY FROM THE ROOFED AREA TO | | | ENSURE THAT NO RAIN WATER WILL TRAVEL TO THE FLOOR | | | DRAINS. |
|