Plan Review Notes
Plan Review Notes For Permit 10060354
Permit Number 10060354
Review Stop ENG
Sequence Number 2
Notes
Date Text
2010-08-02 12:23:23PERMIT COMMENTS:
 REVIEWER: DEAN S. LAUDERMILK, PROJECT COORDINATOR
 CONTACT INFORMATION: DIRECT DIAL: 494-1083, FAX:
 494-1116, EMAIL: [email protected]
 FAILED:
 1) THERE IS NO ROOF OVER THE DUMPSTER PAD. A SANITARY
 SEWER CONNECTION CAN NOT BE MADE TO THE "FLOOR DRAINS"
 UNLESS THE AREA IS COVERED BY A ROOF. TO ALLOW THIS
 AREA TO DRAIN INTO THE SANITARY SEWER SYSTEM WOULD
 ALLOW RAIN WATER ACCESS TO THE SANITARY SYSTEM, WHICH
 IS NOT ALLOWED. THE ONLY WAY A DRAIN SYSTEM FOR THE
 ENCLOSURE CAN BE ALLOWED IS TO HAVE IT ROOFED.
 2) PRIOR TO ALLOWING THE "FLOOR DRAINS" UNDER A ROOF WE
 WOULD NEED TO SEE A SURVEY SHOWING THE GROUND OUTSIDE
 OF THE ROOFED AREA DRAINS AWAY FROM THE ROOFED AREA TO
 ENSURE THAT NO RAIN WATER WILL TRAVEL TO THE FLOOR
 DRAINS.