2010-07-27 10:19:472007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE PLANS DO NOT LIST THE LICENSE NUMBER OF THE
 PERSON RESPONSIBLE FOR THE MECHANICAL SYSTEM DESIGN.
 FBC 13-103.2
  
 2) THE RETURN AIR AS SHOWN ON THE PLANS IS TOO SMALL.
 THE PLANS SPECIFY A LOUVER BIFOLD DOOR ON THE A/C
 CLOSET WHICH IS LOCATED IN BEDROOM #2. THE RETURN AIR
 FROM THE REST OF THE HOUSE WOULD HAVE TO ENTER THE
 BEDROOM THROUGH A 9" TRANSFER DUCT WITH A 10" X 10"
 GRILL. PLEASE CORRECT.
  
 3) THE SIZE OF THE DUCT SUPPLYING BEDROOM #2 IS NOT
 SPECIFIED ON THE PLANS.
  