| Plan Review Notes For Permit 10060348 |
| Permit Number |
10060348 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2010-07-27 10:19:47 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE PLANS DO NOT LIST THE LICENSE NUMBER OF THE | | | PERSON RESPONSIBLE FOR THE MECHANICAL SYSTEM DESIGN. | | | FBC 13-103.2 | | | | | | 2) THE RETURN AIR AS SHOWN ON THE PLANS IS TOO SMALL. | | | THE PLANS SPECIFY A LOUVER BIFOLD DOOR ON THE A/C | | | CLOSET WHICH IS LOCATED IN BEDROOM #2. THE RETURN AIR | | | FROM THE REST OF THE HOUSE WOULD HAVE TO ENTER THE | | | BEDROOM THROUGH A 9" TRANSFER DUCT WITH A 10" X 10" | | | GRILL. PLEASE CORRECT. | | | | | | 3) THE SIZE OF THE DUCT SUPPLYING BEDROOM #2 IS NOT | | | SPECIFIED ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|