2010-07-12 17:01:052007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE EQUIPMENT SIZING CALCULATIONS WERE DONE USING
 WORST-CASE DIRECTIONAL ORIENTATION. SECTION 13-607.AB.1
 OF THE REVISED ENERGY CODE DOES NOT PERMIT THIS. PLEASE
 REVISE.
  
 2) THE MECHANICAL PLANS ARE REQUIRED TO HAVE THE NAME,
 LICENSE NUMBER AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN. FBC SECTION 106.1 AND FS 489.
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORMS.
  
 4) THE ENERGY CALC. FORMS DO NOT SPECIFY THE OWNERS
 NAME OR THE ADDRESS OF THE PROJECT. PLEASE CORRECT.
  