| 2010-07-12 17:01:05 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE EQUIPMENT SIZING CALCULATIONS WERE DONE USING | | | WORST-CASE DIRECTIONAL ORIENTATION. SECTION 13-607.AB.1 | | | OF THE REVISED ENERGY CODE DOES NOT PERMIT THIS. PLEASE | | | REVISE. | | | | | | 2) THE MECHANICAL PLANS ARE REQUIRED TO HAVE THE NAME, | | | LICENSE NUMBER AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. FBC SECTION 106.1 AND FS 489. | | | | | | 3) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | ENERGY CALCULATION FORMS. | | | | | | 4) THE ENERGY CALC. FORMS DO NOT SPECIFY THE OWNERS | | | NAME OR THE ADDRESS OF THE PROJECT. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|