| Plan Review Notes For Permit 10060315 |
| Permit Number |
10060315 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-21 10:46:59 | BUILDING PLAN REVIEW | | | PERMIT: 10060315 | | | ADD: 3800 WASHINGTON SUITE 608 | | | CONT: GLENDON CONST INC | | | TEL: (239)860-2678 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISO: | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED | | | DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL | | | RESULT IN FAILED INSPECTION(S) | | | AND THE ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS | | | REQUIRE ADDITIONAL | | | REVIEWS WITH ASSOCIATED FEES. | | | | | | THE PERMIT APPLICATION INDICATES THE INSTALATION OF | | | FLOOR TILE. PLANS ARE LACKING | | | FLOOR INSULATION REQUIREMENT SEE FBC-B 1207.3 | | | STRUCTURE-BORNE SOUND. | | | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR | | | BETWEEN A DWELLING UNIT AND | | | A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL | | | HAVE AN IMPACT INSULATION | | | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD | | | TESTED) WHEN TESTED IN ACCORDANCE | | | WITH ASTM E 492. | | | | | | | | | |
|