| 2010-07-07 14:31:31 | ****CORRECTIONS**** |
| | ****DCA MODEL FMP4586C***MFGR MODEL ALTHEA*** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. FBC R408.2, SPECIFY VENTILATION OPENING SIZE TO SHOW |
| | COMPLIANCE WITH THE FBC REQUIREMENT, SK02B. |
| | |
| | 2. AN ACCESS/VENTILATION OPENING IS SHOWN AT THE |
| | FOUNDATION MATING LINE BETWEEN MAIN CRAWL SPACE AREA |
| | AND UNDER PORCH AREA, BUT NO VENTILATION OPENING ON THE |
| | OUTSIDE WALL OF THE UNDER PORCH AREA. PLEASE SEE FBC |
| | R408 REGARDING VENTILATION REQUIREMENTS WITHIN 36??? OF |
| | THE CORNERS. |
| | |
| | 3. SK3 EXTERIOR STEM WALL SHOWS 8" MIN FROM GRADE TO |
| | BOTTOM OF FLOOR. SEE FBC R408.4, IF EXTERIOR GRADE IS |
| | AT 8", AN ACCESS AREA COMPLYING WITH FBC R408.4 SHALL |
| | BE PROVIDED. IN ORDER TO AVOID FIELD ISSUES, IT IS |
| | SUGGESTED THAT A DETAIL OR SPECIFICATION WITH SPECIFIC |
| | REQUIREMENTS BE PROVIDED. |
| | |
| | THE FOLLOWING DOES NOT NEED TO BE ADDRESSED, AVISORY |
| | ONLY: |
| | |
| | AFTER ISSUANCE OF THE MASTER, SITE PERMITS WILL |
| | REQUIRE: |
| | |
| | 1. SOILS INVESTIGATION REPORT, 2000 PSF BEARING MINIMUM |
| | 2. CURRENT SURVEY |
| | 3. SITE PLAN SHOWING PROPOSED LOCATION (ZONING REVIEW |
| | REQUIRED) |
| | 4. PROPOSED FINISHED FLOOR ELEVATION FBC403.1.7.3. |
| | 5. STAIR OR DOOR LANDING DETAIL |
| | 6. DETAIL FOR STRUCTURAL CONNECTION BETWEEN MODULES |
| | 7. STRUCTURAL DETAIL FOR GABLE WALL |
| | 8. SEPARATE PERMITS FOR ELECTRIC HOOKUP, PLUMBING |
| | HOOKUP, GAS HOOKUP, MECHANICAL, IMPACT PROTECTION, ROOF |
| | 9. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY, |
| | 561-233-5025. |
| | 10. MASTER PERMIT TO EXPIRE WHEN CODE CHANGES OR ON |
| | 6/9/2011, WHICHEVER IS EARLIER, PER ROBERT C. |
| | SCROGGINS, P.E. LETTER |
| | |