Plan Review Notes
Plan Review Notes For Permit 10060281
Permit Number 10060281
Review Stop B
Sequence Number 1
Notes
Date Text
2010-06-22 14:34:17 
 BUILDING PLAN REVIEW
 PERMIT: 10060281
 ADD: 232 PLYMOUTH RD
 CONT: TO BE DETERMINED
 CONTACT: BRIAN MILLER
 TEL: (561)951-4485
  
 ROOFING PERMIT : 10060286
 CONT: GROUP ONE CONSTRUCTION INC/ CCC 1325796
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 ROOFING PRODUCT APPROVAL SUBMITTED:
 NOA 07-0730.03
 TAMKO MODIFIED BITUMEN ROOF SYSTEM OVER WOOD DECKS
  
 NO SUB-SYSTEM IDENTIFIED NOR FASTENING OPTIONS, ONLY
 SYSTEMS ON PAGES 16 & 17 ARE FOR WOOD
 NON-INSULATED ROOFS.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF
 RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 WILL REQUIRE A REVISION IDENTIFYING SUB-SYSTEM TO BE
 INSTALLED, AND FASTENING OPTION.
 DEPENDING ON THE OPTION -52.5 PSF / -60.0 WILL REQUIRE
 ENHANCED FASTENING FOR ROOF CORNER ZONES (3).
 LIMITATION #7 DOES ALLOW FOR ENHANCED FASTENING PROVIDE
 RAS 117 CALCULATIONS.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  