| 2010-06-15 16:57:19 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2008 |
| | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING |
| | |
| | 1} NOTE #2 ON SHEET #2 INCORRECTLY STATES THAT MOTION |
| | SENSORS ARE NOT REQUIRED FOR BUILDINGS LESS THAN 5000 |
| | SF PER 2007 FBC13-415.AB.1. THAT SECTION SITES OPTIONS |
| | FOR THE REQUIRED AUTOMATIC LIGHTING CONTROLS FOR THE |
| | ENTIRE BUILDING IF OVER 5000 SF. THE SECTION REQUIRING |
| | SPACE CONTROL IS THE FOLLOWING: |
| | |
| | 13-415.AB.1.2 SPACE CONTROL. EACH SPACE ENCLOSED BY |
| | CEILING-HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE |
| | CONTROL DEVICE TO INDEPENDENTLY CONTROL THE GENERAL |
| | LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE SHALL BE |
| | READILY ACCESSIBLE AND LOCATED SO THE OCCUPANTS CAN SEE |
| | THE CONTROLLED LIGHTING. |
| | |
| | A. A CONTROL DEVICE SHALL BE INSTALLED THAT |
| | AUTOMATICALLY TURNS LIGHTING OFF WITHIN 30 MINUTES OF |
| | ALL OCCUPANTS LEAVING A SPACE, EXCEPT SPACES WITH |
| | MULTISCENE CONTROL, IN THE FOLLOWING: |
| | |
| | 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| | LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| | CLASSROOMS). |
| | |
| | 2. CONFERENCE/MEETING ROOMS. |
| | |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | |
| | THESE SPACES ARE NOT REQUIRED TO BE CONNECTED TO OTHER |
| | AUTOMATIC LIGHTING SHUTOFF CONTROLS. |
| | |
| | TO FACILITATE THE ISSUANCE OF THIS PERMIT THIS REVIEW |
| | IS APPROVED WITH EXCEPTION AND A REVISION IS REQUIRED |
| | TO CORRECT THE ABOVE LISTED DEFICIENCY. |
| | |
| | THIS REVISION IS REQUIRED TO BE SUBMITTED AND APPROVED |
| | PRIOR TO THE FIRST ELECTRICAL INSPECTION. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |
| | |