Plan Review Notes
Plan Review Notes For Permit 10060231
Permit Number 10060231
Review Stop Z
Sequence Number 1
Notes
Date Text
2010-06-25 17:15:58FAILED
  
 1) IT IS UNCLEAR WHAT THE SCOPE OF WORK IS FOR THIS
 PERMIT. IT APPEARS THERE IS AN ADDITION TO THE FRONT
 AND THE WEST SIDE OF THE HOUSE.
  
 2) THE ADDITION(S) SHALL BE SHOWN ON THE SURVEY, WITH
 THE FINAL SETBACKS PROVIDED.
  
 3) THE FRONT ADDITION APPEARS TO ENCROACH INTO THE
 REQUIRED 25 FOOT FRONT SETBACK. THE EXISTING HOUSE IS
 SHOWN WITH A 25.1 FOOT FRONT SETBACK. A MINIMUM 25 FOOT
 SETBACK IS REQUIRED, THEREFORE ONLY A 0.1 FOOT
 EXPANSION IS ALLOWED.
  
 4) THE WEST SIDE ADDITION VIOLATES THE 15 FOOT TOTAL
 SIDE SETBACK REQUIREMENT AND MAY NOT BE CONSTRUCTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.