| 2010-06-29 11:17:51 | BUILDING PLAN REVIEW |
| | PERMIT: 10060231 |
| | ADD: 522 SUNSET ROAD |
| | CONT: O/B WAITE, ALISSA |
| | TEL: (561)632-1779 |
| | |
| | |
| | RES BLD CODE= 2007 FLORIDA RESIDENTIAL BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS DO NOT INDICATE TO WHAT CODES THEY WERE |
| | DESIGNED TO OR TO WHICH EDITION. |
| | THIS REVIEW WILL BE UNDER THE: |
| | 2007 FLORIDA EXISTING BUILDING CODE W/ 2009 |
| | SUPPLEMENTS, CHAPTER 10 ADDITIONS & |
| | 2007 FLORIDA RESIDENTIAL CODE W/ 2009 SUPPLEMENTS |
| | PLEASE UPDATE PLANS. |
| | |
| | 2) PLANS ARE ALSO LACKING THE DESIGN CRITERIA: |
| | R301.2- R301.7 |
| | THIS ALSO INCLUDES WIND DESIGNS FBC-B 1609.6.2 WIND |
| | DESIGN PROCEDURES |
| | 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | |
| | 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | |
| | 3) SHEET 2 IS THE FOUNDATION DESIGN WHICH INDICATES |
| | THREE REBARS BUT THE DEPTH LOCATION HAS NOT BEEN |
| | PROVIDED? IN A TWO BAR SYSTEM THE TWO BAARS ARE LOCATED |
| | IN THE BOTTOM 1/3 RD OF THE FOUNDATION, WITH A THREE |
| | BAR SYSTEM THE ADDITIONAL THIRD BAR IS LOCATED IN THE |
| | UPPER THIRD OF THE FOUNDATION PLEASE PROVIDE WHERE THE |
| | FOOTER DESIGN WAS DERIVED FROM? |
| | |
| | 4) SHEET 3: |
| | |
| | 4A) THIS WALL SECTION INDICATES A CONCRETE HEADER AND |
| | FILLED CELL WITH 2500 PSI CONCRETE. IT APPEARS THAT THE |
| | DESIGNER IS MIXING A GROUTED MASONRY SYSTEM WHICH WOULD |
| | USE A |
| | BEAM BLOCK VERSES A 8X16 CONCRETE POURED CONCRETE BEAM? |
| | PLEASE REVIEW R-609 FOR GROUT PLACEMENT, CLEAN OUTS, IF |
| | USING BOND BEAM AND REINFORCING R-609.2. |
| | PLEASE ALSO BE AWARE OF THE REQUIREMENT FOR GABLES TO |
| | HAVE EITHER END BRACING OR RAKED BEAMS SEE FIGURE |
| | R609.4 & R609.4.1. WILL A LINTEL BE INCORPORATED OVER |
| | THE NEW WINDOW, IF PLEASE PROVIDE PRODUCT APPROVAL. |
| | |
| | IF USING THE 8X16 POURED CONCRETE BEAM PLEASE PROVIDE |
| | STRENGHT OF CONCRETE, SIZE OF REBAR AS WELL AS NUMBER |
| | OF RE-BARS IN THE UPPER AND LOWER SECTION OF BEAM, AT |
| | WINDOW PLEASE PROVIDE EITHER THE HOOP OR STIRRUP SIZE |
| | OF REBAR, SIZE OF UNIT AND SPACING OF HOOPS OR STIRRUPS |
| | ACI 530.7.5.3.1. |
| | |
| | 4B) SUBMITTED ARE VARIOUS PRODUCT APPROVALS FOR VARIOUS |
| | TYPE OF HANGERS AND OR STRAPS, BUT THE PLANS DO NOT |
| | PROVIDE THE LOCATION WHERE THEY WILL BE INSTALLED. THE |
| | PLANS INDICATE 2X6 FLOOR JOIST BUT NO SPACING IS |
| | PROVIDED NOR LEDGER OR HEADERS TO SECURE THE FLOOR |
| | SYSTEM TO THE CBS WALL SYSTEM. |
| | |
| | 4C) PLEASE PROVIDE DETAILS FOR THE 2X12 RAFTERS HOW THE |
| | UPPER PORTION WILL BE SURED TO THE EXISTING WALL? |
| | PROVIDE HOW THE NEW ROOFING WILL ALSO BE FLASHED AT THE |
| | EXISTING WALL LINE? |
| | |
| | 4D) THE PLANS INDICATE THERE TO BE A OPEN CEILING OR |
| | WILL THER BE A DROPED CEILING FRAMING OF WHAT MATERIAL, |
| | SIZE AND SPACING AND TYPE OF CEILING MATERIAL? |
| | |
| | 5) PLANS DO NOT INDICATE THE USAGE OF THIS ROOM IF IT |
| | IS TO BE CONSIDERED A SLEEPING ROOM THE REQUIREMENTS OF |
| | R-310.1. |
| | |
| | 6) PLANS DO NOT INDICATE IF WOOD BUCKS ARE TO BE |
| | INSTALLED IF SO PLEASE REVIEW R613.6.1.1. |
| | |
| | 7) THE WINDOW APPROVAL SUBMITTED NOA 09-0316.09 |
| | INDICATES FOR MULTIPLE UNITS A MULLION WILL BE |
| | REQUIRED, WHICH IS NOT PART OF THIS APPROVAL. SEE TOP |
| | NOTES ON SHEET 1 OF 5.R6.13.7. |
| | |
| | 8) THE ROOFING NOA SUBMITTED PLEASE CIRCLE WHICH |
| | SUB-SYSTEM IS TO BE INSTALLED ON THIS ADDITION THERE |
| | ARE 2 SUB-SYSTEMS WITH VERY DIFFERENT PRESSURES. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 9) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES |
| | DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER |
| | NOTICE. |
| | |
| | OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM |
| | - 5:00 PM. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |