Plan Review Notes
Plan Review Notes For Permit 10060221
Permit Number 10060221
Review Stop E
Sequence Number 1
Notes
Date Text
2010-06-14 12:55:49 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2008 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122.
  
 2} 210.52 (E)(1) ONE-FAMILY AND TWO-FAMILY DWELLINGS.
 FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET ACCESSIBLE WHILE STANDING AT GRADE
 LEVEL AND LOCATED NOT MORE THAN 2.0 M (61/2 FT) ABOVE
 GRADE SHALL BE INSTALLED AT THE FRONT AND BACK OF THE
 DWELLING.***NO RECEPTACLE IS LOCATED IN THE FRONT OF
 THE RESIDENCE.
  
 3} THE "OPTIONAL" WHIRLPOOL AND WINE COOLER REF. SHOWN
 ON THE PLAN SHOULD BE LISTED IN THE AND CALCULATED IN
 THE PANEL SCHEDULE.408.4, 220, 2008 NEC.
  
 4} THE LOCATION OF THE CONDESING UNITS MAY NOT COMPLY
 WITH THE WORKING CLEARANCE REQUIREMENTS FOR THE SERVICE
 AND DISCONNECTS PER 110.26.
  
 NOTE: THESE ITEMS WOULD HAVE BEEN REDLINED BY THE
 REVIEWER TO EXPEDITE THE START OF THE PROJECT IF THIS
 PLAN WAS NOT INTENDED TO BE MASTERED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  