| Plan Review Notes For Permit 10060221 |
| Permit Number |
10060221 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-06-21 09:28:29 | 2007 FBC W/2009 REVISIONS | | | NSFR | | | | | | DENIED BY BUILDING | | | | | | 1) BEFORE A PERMIT TO CONSTRUCT CAN BE | | | ISSUED, IMPACT FEES MUST BE PAID TO | | | PALM BEACH COUNTY. THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION. 233-5025 | | | | | | 2) THE STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C AND | | | THE PLANS SPECIFY EXPOSURE B. PLEASE CORRECT THE | | | EXPOSURE AND INCREASE WINDLOAD PRESSURES ACCORDINGLY. | | | REVIEW PRODUCT APPROVALS FOR THE INCREASED PRESSURE | | | REQUIREMENTS. | | | | | | 3) PROVIDE COPIES OF SUBDIVISION COVENANTS THAT ALLOW | | | EMERGENCY EGRESS FROM THE BEDROOMS ON THE ZERO LOT LINE | | | ACROSS THE ADJACENT PROPERTY TO THE PUBLIC WAY. FBC | | | R310 | | | | | | 4) ON SHEET A1 THE ATTIC ACCESS DETAIL SPECIFIES R-11 | | | INSULATION AND THE ENERGY CALCULATION REQUIRES R-30. | | | PLEASE CORRECT. | | | | | | 5) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE ONE HOUR | | | FIRE RATED GLASS BLOCK, REQUIRED ON THE ZERO LOT LINE. | | | DCA RULE 9B-72. | | | | | | 6) SUBMIT 2 SETS OF PRODUCT APPROVALS FOR THE HURRICANE | | | STRAPS AND CONNECTORS AS REQUIRED BY DCA RULE 9B-72. | | | THE FLORIDA PRODUCT APPROVAL NUMBERS OR MIAMI DADE NOA | | | NUMBERS CAN BE LISTED WITH THE CONNECTORS IN THE TRUSS | | | CONNECTOR SCHEDULE ON THE PLANS. | | | | | | 7) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. FBC | | | 106.3.3 CITY AMENDMENTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|