2010-08-23 15:00:36****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1-2. ADDRESSED.
  
 3. FROM PREVIOUS LIST - SHOW HOW EXITING IS AFFECTED,
 FBC10. DECLARE OCCUPANCY CLASSIFICATION FOR EACH AREA,
 AND SHOW HOW EXITING IS AFFECTED. IT APPEARS THAT YOU
 ARE CREATING A NEW EGRESS PATH, NOT CLEAR WHERE THE
 EXIT IS, OCCUPANT LOAD NOT STATED, HOW WILL THE
 ADDITIONAL OCCUPANTS WHICH MAY ELECT TO EXIT IN THIS
 DIRECTION AFFECT THE CURRENT EXITING CAPACITY? HOW WILL
 EXIT LIGHTING BE AFFECTED?
  
  
  
  
  